Xanbus Automatic Generator Start Installation

Type 11

Type 11 is a two-wire run mode configuration. It requires only two wires and one relay to control the generator. Relay 1 closes momentarily once to start the generator, and closes momentarily again to stop the generator.

AGS Harness W ires

 

Generator W ires

 

12

 

GENERATOR RUN SIGNAL

 

13

 

GENERATOR RUN SIGNAL RETURN

Relay 1

14

5A fuse

RUN

16

 

 

 

 

 

For additional information, see “Circuit Limitations” on page 11.

Figure 19 Type 11 Connection Diagram

Relay Function

Preset Configuration Setting

 

 

Relay 1 mode

MomentaryRun

Relay 3 mode

No function

Gen Run signal hold time

0.5 s

Preheat time

0 s

Preheat to crank delay

0 s

Crank time

10 s

Crank retry time

15 s

Gen Cool Down

30 s

 

 

Relay Function

Preset Configuration Setting

 

 

Gen Spin Down

3 s

Shutdown bypass time

0 s

Start tries

3

 

 