Xanbus Automatic Generator Start Installation

Type 4

Type 4 is a three-wire StartStop configuration that uses relay 3 to provide a 60-second preheat signal.

AGS Harness W ires

Generator W ires

Relay Function

Preset Configuration Setting

 

 

Preheat to crank delay

5 s

 

 

Crank time

15 s

 

 

Crank retry time

15 s

Relay 1

Relay 2

Relay 3

12

13

14

16

17

18

19

20

 

 

 

 

GENERATOR RUN SIGNAL

 

 

 

 

 

 

 

 

GENERATOR RUN SIGNAL RETURN

 

 

 

5A fuse

 

 

 

STOP/PREHEAT

 

 

 

 

 

 

 

 

 

 

 

5A fuse

START

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5A fuse FUEL PRIME (PREHEAT)

12V GENERATOR BATTERY+

Gen Cool Down

30 s

 

 

Gen Spin Down

3 s

 

 

Shutdown bypass time

0 s

 

 

Start tries

3

For additional information, see “Circuit Limitations” on page 11.

Figure 10 Type 4 Connection Diagram

Relay Function

Preset Configuration Setting

 

 

Relay 1 mode

StartStop

Relay 3 mode

Preheat

 

 

Gen Run signal hold time

10 s

 

 

Preheat time

60 s

 

 

18

Xanbus Automatic Generator Start (AGS) Owner’s Guide

Page 28
Image 28
Xantrex Technology 809-0915 manual Type 4 Connection Diagram