Xanbus Automatic Generator Start Installation

Type 8

Type 8 will work with both two-wire and three-wire run mode configurations. Type 8 is identical to Type 7 except that it provides no preheat signal before cranking.

AGS Harness W ires

 

Generator W ires

 

12

 

GENERATOR RUN SIGNAL

 

13

 

GENERATOR RUN SIGNAL RETURN

Relay 1

14

5A fuse

RUN

16

 

 

 

 

 

For additional information, see “Circuit Limitations” on page 11.

Figure 15 Type 8 Connection Diagram (two-wire)

AGS Harness W ires

Generator W ires

Relay Function

Preset Configuration Setting

 

 

Relay 1 mode

Run

 

 

Relay 3 mode

No function

 

 

Gen Run signal hold time

0.5 s

 

 

Preheat time

0 s

 

 

Preheat to crank delay

0 s

 

 

Crank time

15 s

 

 

Crank retry time

30 s

 

 

Gen Cool Down

30 s

 

 

Gen Spin Down

3 s

 

 

Shutdown bypass time

0 s

Relay 1

12

13

14

16

 

 

 

 

GENERATOR RUN SIGNAL

 

 

 

 

 

 

 

 

GENERATOR RUN SIGNAL RETURN

 

 

 

5A fuse

 

 

 

RUN

 

 

 

 

 

 

 

 

 

 

 

 

 

Start tries

3

Relay 2

17

18

5A fuse

START

For additional information, see “Circuit Limitations” on page 11.

Figure 16 Type 8 Connection Diagram (three-wire)

22

Xanbus Automatic Generator Start (AGS) Owner’s Guide