Xantrex Technology 809-0915 manual AGS Configuration Menu Contents

Models: 809-0915

1 100
Download 100 pages 27.4 Kb
Page 49
Image 49

Configuration of the Xanbus AGS

When the AGS Home Screen is first displayed, the menu defaults to the

GenMode Menu. If configuration changes need to be made, the

Configuration Menu can be accessed by pressing the Enter, Up arrow, and

Down arrow buttons all at same time to access the Advanced Settings.

AC In/Charge

XAGS 00: Setup

STBY/ON

 

Inverter On

 

GenMode

[ManualOff]

Fault Clear

 

Low Battery

Mode

[Operating]

Xanbus AGS Menu

Fault

Clear Faults Warnings

View Device Info

 

 

 

 

 

XAGS 00: Setup

 

 

 

Advanced Settings

 

 

 

GenMode

[ManualOff]

 

Enter

Func

Clear Faults Warnings

 

 

 

View Device Info

Xanbus System Control Panel (SCP)

 

FGA: 809-0921

 

 

 

 

XAGS 00: Setup

 

 

To access the Advanced Settings menu,

 

 

 

Press Enter and Up and Down arrows together Advanced Settings

 

 

 

GenMode

[ManualOff]

Clear Faults Warnings

View Device Info

XAGS 00: Config

QT EN

[Enabled]

 

 

QT Begin

[9:00PM]

 

 

QT End

[8:00AM]

 

 

Gen Type

[2]

 

 

Cfg Trigger

 

 

 

 

 

 

Cfg Gen

 

 

 

 

Multi-Unit Config

Restore Defaults

To change configuration parameters...

Press Enter to move forward into the Config menu.

XAGS 00: Triggers

Start DCV 30 Sec

[40.0V]

Start DCV 15 Sec

[Disabled]

Start DCV 2 hr

[Disabled]

Start DCV 24 Hr

[Disabled]

Stop Float

[Disabled]

Stop Absorb

[Disabled]

StopV

[Disabled]

Temp1

[Disabled]

Temp2

[Disabled]

Load

[Disabled]

Start Load

[15A]

Stop Load

[10A]

XAGS 00: Gen

 

Starter Cool Down

[60sec]

Gen Cool Down

[30sec]

Gen Spin Down

[3sec]

Max Runtime

[4hours]

Exercise per

[21days]

Exercise Dur

[30min]

Exercise Time

[9:00AM]

Relay 3

[Not Used]

Gen Run Hold Time

[0.5s]

Crank Delay

[1sec]

Crank Time

[30sec]

Use these buttons to change the settings.

Press ENTER to accept the new setting.

To return to the B asic Settings menu,

Press Enter and Up and Down arrows together

Use these buttons to select the desired menu.

Press ENTER to move the cursor to the changeable settings.

Press Func to return to the Xanbus AGS Home screen.

Crank Retry Time

[40sec]

 

Preheat Time

[0sec]

 

Gen Start Tries

[3]

 

 

 

 

 

XAGS 00: Gen

 

 

Dev Name

[AGS]

 

Dev Number

[00]

 

Connections

 

 

 

 

 

 

 

XAGS 00: Conn

DC Conn

[HouseBatt1]

AC In

[Grid1]

AC Out

[ACLoad]

Generator

[Gen1]

Figure 32 AGS Configuration Menu Contents

975-0082-01-01

39

Page 49
Image 49
Xantrex Technology 809-0915 manual AGS Configuration Menu Contents