Xanbus Automatic Generator Start Installation

Type 7

Type 7 will work with both two-wire and three-wire run mode configurations that require a preheat signal before cranking. This Gen Type setting is suitable for generators with an automatic engine cranking control system (two-wire) and generators that require that the AGS control their starter separately (three- wire).

AGS Harness W ires

 

Generator W ires

 

12

 

GENERATOR RUN SIGNAL

 

13

 

GENERATOR RUN SIGNAL RETURN

Relay 1

14

5A fuse

RUN

16

 

 

 

 

 

For additional information, see “Circuit Limitations” on page 11.

Figure 13 Type 7 Connection Diagram (two-wire)

AGS Harness W ires

Generator W ires

Relay Function

Preset Configuration Setting

 

 

Relay 1 mode

Run

Relay 3 mode

No function

Gen Run signal hold time

0.5 s

Preheat time

20 s

Preheat to crank delay

1 s

Crank time

15 s

Crank retry time

30 s

Gen Cool Down

30 s

Gen Spin Down

3 s

Shutdown bypass time

0 s

Start tries

3

 

 

Relay 1

12

13

14

16

 

 

 

 

GENERATOR RUN SIGNAL

 

 

 

 

 

 

 

 

GENERATOR RUN SIGNAL RETURN

 

 

 

5A fuse

 

 

 

RUN

 

 

 

 

 

 

 

 

 

 

 

 

 

Relay 2

17

18

5A fuse

START

For additional information, see “Circuit Limitations” on page 11.

Figure 14 Type 7 Connection Diagram (three-wire)