Xanbus Automatic Generator Start Installation

Type 12

Type 12 is a three-wire GlowStop configuration recommended for “three- wire” generators that don’t require a dedicated preheat signal. In this configuration, the start signal is applied for longer because the generator does its own preheat and cranking while the start signal is applied.

AGS Harness W ires

Generator W ires

Relay Function

Preset Configuration Setting

 

 

Crank retry time

40 s

 

 

Gen Cool Down

30 s

 

 

Gen Spin Down

3 s

 

 

Shutdown bypass time

0 s

Relay 1

Relay 2

12

13

14

16

17

18

GENERATOR RUN SIGNAL GENERATOR RUN SIGNAL RETURN

5A fuse

STOP

5A fuse

START

Start tries

3

For additional information, see “Circuit Limitations” on page 11.

Figure 20 Type 12 Connection Diagram

Relay Function

Preset Configuration Setting

 

 

 

 

Relay 1 mode

GlowStop

 

Relay 3 mode

No function

 

 

 

 

Gen Run signal hold time

4 s

 

 

 

 

Preheat time

0 s

 

 

 

 

Preheat to crank delay

0 s

 

 

 

 

Crank time

30 s

 

 

 

 

 

 

 

26

Xanbus Automatic Generator Start (AGS) Owner’s Guide

Page 36
Image 36
Xantrex Technology 809-0915 manual Type 12 Connection Diagram