Crank Delay
Purpose "Crank Delay" specifies the delay time from when the preheat relay is
Values | Default |
|
|
0s to 250s | 1s |
|
|
Considerations This setting is automatically configured when a "Gen Type" is selected for the generator. Manually change this setting only on the advice of the generator manufacturer or authorized service personnel.
Crank Time
Purpose "Crank Time" specifies the maximum length of time the Start relay is engaged (and cranking the starter motor) for the first attempt to start the generator.
Values | Default |
|
|
0s to 250s (increments of 1s) | 30s |
|
|
Considerations This setting is automatically configured when a "Gen Type" is selected for the generator. Manually change this setting only on the advice of the generator manufacturer or authorized service personnel.
Crank Retry Time
Purpose "Crank Retry Time" specifies the length of time the Start relay is engaged (and cranking the starter motor) for the second and subsequent attempts to start the generator, in cases when the generator fails to start on the first attempt.
Values | Default |
|
|
0s to 250s (increments of 1s) | 40s |
|
|
Considerations This setting is automatically configured when a "Gen Type" is selected for the generator. Manually change this setting only on the advice of the generator manufacturer or authorized service personnel.
Preheat Time
Purpose "Preheat Time" specifies how long the Preheat relay is engaged during the start sequence. The preheat signal may be required for diesel generators with glow plugs or fuel priming for gas generators.
The Preheat relay may be Relay 1 or Relay 3, depending on the "Relay3" setting or the Gen Type selected.
Values | Default |
|
|
0s to 250s (increments of 1s) | 0s |
|
|
Considerations This setting is automatically configured when a "Gen Type" is selected for the generator. Manually change this setting only on the advice of the generator manufacturer or authorized service personnel.