Configuration of the Xanbus AGS

User Settings

Use this table to record any customized AGS settings for future reference.

Table 5 Generator Configuration Settings, Values, Defaults, and User Settings

Setting

 

Values

Default

User

 

 

 

 

Setting

 

 

 

 

 

Main Menu Items:

 

 

 

 

GenMode

 

ManualOn, ManualOff, Automatic

ManualOff

 

Mode

 

Operating/Standby

Operating

 

Configuration Menu

Items:

 

 

"QT En"

 

Enabled, Off

Enabled

 

"QT Begin"

 

12:00AM–11:59PM (12-hour

9:00PM (12-hour

 

 

 

clock)

clock)

 

 

 

00:00–23:59 (24-hour clock)

21:00 (24-hour clock)

 

"QT End"

 

12:00AM–11:59PM (12-hour

8:00AM (12-hour

 

 

 

clock)

clock)

 

 

 

00:00–23:59 (24-hour clock)

8:00 (24-hour clock)

 

"Gen Type"

 

Type 1 to Type 14

Type 2

 

Triggers Menu Items:

 

 

 

 

"Start DCV 30

 

Disabled, 4.0 V–60.0 V

11.3 V

 

sec"

 

 

 

 

"Start DCV 15

 

Disabled, 4.0 V–60.0 V

Disabled

 

min"

 

 

 

 

"Start DCV 2

 

Disabled, 4.0 V–60.0 V

Disabled

 

hr"

 

 

 

 

"Start DCV 24

 

Disabled, 4.0 V–60.0 V

Disabled

 

hr"

 

 

 

 

"Stop Float"

 

Enabled, Disabled

Disabled

 

"Stop Absorb"

 

Enabled, Disabled

Enabled

 

"Stop V"

 

Disabled, 4.0 V–65.0 V

Disabled

 

"Temp1"

 

Enabled, Disabled

Disabled

 

Table 5 Generator Configuration Settings, Values, Defaults, and User Settings

Setting

Values

Default

User

 

 

 

Setting

 

 

 

 

"Temp2"

Enabled, Disabled

Disabled

 

"Load"

Enabled, Disabled

Disabled

 

"Start Load"

10.0 A–33.0 A

10.0 A

 

"Stop Load"

7.0 A–28.0 A

7.0 A

 

Generator Menu Items:

 

 

"Starter Cool

1s to 250s (increments of 1s)

60s

 

Down"

 

 

 

"Gen Cool Down"

0s to 90 s (increments of 1s)

30s

 

"Gen Spin Down"

0s to 900s (increments of 1s)

3s

 

"Max Run Time"

0hours–24 hours

8hours

 

"Exercise Per"

0days (Off)–250days

21days

 

"Exercise Dur"

1min–250min

30min

 

"Exercise Time"

12:00AM–11:59PM (12-hour

9:00AM (12-hour

 

 

clock)

clock)

 

 

00:00–23:59 (24-hour clock)

9:00 (24-hour clock)

 

"Relay3"

Preheat, WrmupCoolDn, Preheat

NotUsed

 

 

SDByp, NotUsed

 

 

"Gen Run Hold

0.5s to 20s (increments of 1s)

0.5s

 

Time"

 

 

 

"Crank Delay"

0s to 60s (increments of 1s)

0s

 

"Crank Time"

0s to 250s (increments of 1s)

30s

 

"Crank Retry

0s to 250s (increments of 1s)

40s

 

Time"

 

 

 

"Preheat Time"

0s to 250s (increments of 1s)

0s

 

"Gen Start

1 to 10

3

 

Tries"

 

 

 

 

 

 

 

975-0082-01-01