Xantrex Technology 809-0915 Starting and Stopping the Generator, To start the generator manually

Models: 809-0915

1 100
Download 100 pages 27.4 Kb
Page 75
Image 75

Operation of the Xanbus AGS

Starting and Stopping the Generator

Use the AGS to start or stop the generator manually using the Xanbus System Control Panel (SCP) or automatically in response to an electrical system condition.

To set the AGS to start and stop the generator automatically:

1.On the AGS menu, highlight GenMode and press Enter.

2.Use the arrow button to select [Automatic].

3.Press Enter.

To start the generator manually:

1.On the AGS menu, highlight GenMode and press Enter.

2.Use the arrow button to select [ManualOn].

3.Press Enter.

To stop the generator manually:

1.On the AGS menu, highlight GenMode and press Enter.

2.Use the arrow button to select [ManualOff].

3.Press Enter.

IMPORTANT: To avoid AGS faults, try not to combine automatic and external manual starts and stops.

When the generator has been started automatically, allow it to stop automatically unless a situation occurs that requires the generator to be stopped urgently.

Likewise, if the generator has been started manually, ensure that it is stopped manually. Only the "Max Run Time" setting can automatically stop the generator after it has been started manually.

FSW System Home Screen

 

Select Device Menu

AGS Menu

 

 

System Status

 

 

 

 

Select Device

 

XAGS 00: Setup

 

Battery

20.4A

53.9V

 

 

 

System Settings

GenMode

[ManualOff]

 

BatLev

 

 

 

E--F

 

 

 

FSW3012

Mode

[Operating]

 

Load

 

 

 

1235W

 

 

 

EMS

 

 

Clear Faults Warnings

 

AC1

1150W

3202V

 

 

 

XAGS

 

 

 

View Device Info

Menu

Figure 34 Starting and Stopping the Generator