Troubleshooting

Fault Reference Table

When the AGS detects a fault condition, it stops the generator. The red Fault light also comes on, and the Xanbus System Control Panel (SCP) displays a fault message.

The AGS remembers the GenMode that it was in at the time it detected the fault. After you have cleared the fault, the AGS returns to its last known GenMode.

Table 7

AGS Fault Messages

 

 

 

 

 

 

 

Fault

Message

Self-clearing?

Cause

Action

Number

 

 

 

 

 

 

 

 

 

F200

Exceeded

No

The AGS has tried and

Check the generator’s

 

max number

 

failed to start the

fuel level and start

 

of start tries.

 

generator. To prevent

battery condition.

 

Check gen,

 

draining the start

Consult generator

 

clear fault.

 

battery, the AGS will

manual.

 

 

 

suspend further start

Clear fault on System

 

 

 

attempts.

Control Panel screen to

 

 

 

 

allow retry.

 

 

 

 

 

F201

Unable to

No

The AGS has lost

Change the AGS mode

 

stop gen.

 

contact with the

to Manual Off.

 

Stop gen via

 

generator or the

If this fails to work,

 

its control

 

generator did not stop

stop the generator with

 

panel.

 

after the AGS sent it a

the external stop

 

 

 

stop signal.

switch.

 

 

 

 

Check generator.

 

 

 

 

Return AGS to

 

 

 

 

automatic mode to

 

 

 

 

resume automatic starts

 

 

 

 

and stops.

 

 

 

 

 

Table 7

AGS Fault Messages

 

 

 

 

 

 

 

Fault

Message

Self-clearing?

Cause

Action

Number

 

 

 

 

 

 

 

 

 

F203

Manual Off:

No

An external sensor

After the sensor

 

Gen stopped

 

connected to the AGS

connected to the

 

by ext

 

has stopped the

external shutdown has

 

sensor. Reset

 

generator and put the

deactivated, clear the

 

GenMode.

 

AGS into Manual Off

fault and reset the AGS

 

 

 

mode.

to the desired mode.

 

 

 

 

 

F500

Serial

No

The silicon serial ID

Call your dealer or

 

Number

 

number has failed and

Xantrex Technology

 

Failure,

 

the AGS has gone into

USA Inc.

 

Service

 

Standby.

 

 

Required.

 

 

 

 

 

 

 

 

F501

Memory

No

The AGS has suffered a

Call your dealer or

 

Failure.

 

non-volatile memory

Xantrex Technology

 

Service

 

failure.

USA Inc.

 

Required.

 

 

 

 

 

 

 

 

F505

Internal

No

A controller fault has

Clear the fault. If the

 

Failure.

 

occurred and the AGS

fault persists, call your

 

Service

 

has gone into Standby.

dealer or Xantrex

 

Required.

 

 

Technology USA Inc.

 

 

 

 

 