Xantrex Technology 809-0915 manual Exercise Dur, Exercise Time

Models: 809-0915

1 100
Download 100 pages 27.4 Kb
Page 66
Image 66

Configuration of the Xanbus AGS

Exercise Dur

Full name Exercise Duration (in minutes)

Purpose "Exercise Dur" sets how long the generator will run when it is exercised.

Dependencies The "Exercise Dur" trigger requires that any parameter other than “0” be set in "Exercise Per" and a time of day be set in the "Exercise Time" trigger.

Values

Default

 

 

1min to 250min

30min

 

 

IMPORTANT: Ensure that the Exercise Duration is not set for longer than the "Max Run Time" setting. Attempting to do so will generate a warning on the System Control Panel.

IMPORTANT: Consult the generator manual or a service representative from the generator’s manufacturer for the recommended exercise duration.

Exercise Time

Purpose "Exercise Time" sets the time of day that the AGS exercises the generator.

The "Exercise Time" trigger requires that any parameter other than “0” be set in "Exercise Per" and a value be set in the "Exercise Dur" trigger.

Values

Default

 

 

12:00AM to 11:50PM (12-hour clock)

9:00AM

00:00 to 23:50 (24-hour clock)

 

(increments of 10 minutes)

 

 

 

Considerations If the Exercise Time is set, the generator will start at that time after being inactive for the Exercise Period.

If the Exercise Time occurs during Quiet Time, the generator will start when Quiet Time is over and run for the full amount of time set for

"Exercise Dur".

56

Xanbus Automatic Generator Start (AGS) Owner’s Guide

Page 66
Image 66