Xanbus Automatic Generator Start Installation
Type 2
Type 2 is a
AGS Harness W ires | Generator W ires |
Relay Function | Preset Configuration Setting |
|
|
Crank time | 30 s |
|
|
Crank retry time | 40 s |
|
|
Gen Cool Down | 30 s |
|
|
Gen Spin Down | 3 s |
|
|
Shutdown bypass time | 0 s |
Relay 1
12
13
14
16
GENERATOR RUN SIGNAL GENERATOR RUN SIGNAL RETURN
5A fuse | STOP/PREHEAT |
Start tries | 3 |
Relay 2
17
18
5A fuse | START |
For additional information, see “Circuit Limitations” on page 11.
Figure 8 Type 2 Connection Diagram
Relay Function | Preset Configuration Setting |
|
|
Relay 1 mode | GlowStop |
Relay 3 mode | No function |
|
|
Gen Run signal hold time | 0.5 s |
|
|
Preheat time | 0 s |
|
|
Preheat to crank delay | 0 s |
|
|
16 | Xanbus Automatic Generator Start (AGS) Owner’s Guide |