Xantrex Technology 809-0915 manual QT End, Gen Type

Models: 809-0915

1 100
Download 100 pages 27.4 Kb
Page 52
Image 52

Configuration of the Xanbus AGS

QT End

Full name Quiet Time End

Purpose "QT End" is a changeable setting that defines the end of quiet time.

This setting also requires a setting for "QT Begin".

Dependencies "QT End" functions only if the AGS is in Automatic mode. This setting requires "QT En" be set to [Enabled] and also requires a setting for "QT Begin".

Ensure the clock on the Xanbus System Control Panel (SCP) is set to the correct local time.

Gen Type

Full name Generator Type

Purpose "Gen Type" selects the starting requirements of the generator. The starting requirements determine how the AGS must be wired to the generator’s starting system. For more information, see “Connecting the Generator” on page 14 or Appendix B.

IMPORTANT: "Gen Type" can only be changed after the system is put into Standby. See “Putting the AGS in Standby Mode” on page 67.

Table 4 Generator Type Descriptions

Value

Description

 

 

12:00AM to

At the time set for "QT End" the AGS will be

11:59PM (12-hour

able to automatically start the generator again. If

clock)

a start trigger has occurred during quiet time and

00:00 to 23:59

is still active, the generator will start immediately

(24-hour clock)

after quiet time ends.

 

 

 

Description

 

 

 

 

Option

Mode

For Technical Details, see.a

 

 

 

Type 1

GlowStop

page 15

 

 

 

Type 2

GlowStop with no preheat

page 16

 

 

 

Type 3

GlowStop with shutdown bypass

page 17

 

 

 

Type 4

StartStop with Relay 3 prime

page 18

 

 

 

Type 5

StartStop with Relay 3 preheat

page 19

 

 

 

Type 6

GlowStop with normally closed RunStop contact

page 20

 

 

 

Type 7

Run with preheat

page 21

 

 

 

Type 8

Run with no preheat

page 22

 

 

 

Type 9

StartStop with Relay 3 preheat and shutdown

page 23

 

bypass

 

Type 10

StartStop

page 24

 

 

 

Type 11

MomentaryRun

page 25

 

 

 

42

Xanbus Automatic Generator Start (AGS) Owner’s Guide

Page 52
Image 52
Xantrex Technology 809-0915 manual QT End, Gen Type