Xantrex Technology 809-0915 manual Type 9 Connection Diagram

Models: 809-0915

1 100
Download 100 pages 27.4 Kb
Page 33
Image 33

Xanbus Automatic Generator Start Installation

Type 9

Type 9 is a StartStop mode configuration with shutdown bypass functionality on relay 3.

Relay Function

Preset Configuration Setting

 

 

Crank time

15 s

 

 

Crank retry time

30 s

AGS Harness W ires

Generator W ires

Relay 1

Relay 2

Relay 3

12

13

14

16

17

18

19

20

 

 

 

 

GENERATOR RUN SIGNAL

 

 

 

 

 

 

 

 

GENERATOR RUN SIGNAL RETURN

 

 

 

5A fuse

 

 

 

STOP

 

 

 

 

 

 

 

 

 

 

 

5A fuse

START

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5A fuse FUEL PRIME (PREHEAT)

12V GENERATOR BATTERY+

Gen Cool Down

30 s

 

 

Gen Spin Down

3 s

 

 

Shutdown bypass time

5 s

 

 

Start tries

3

For additional information, see “Circuit Limitations” on page 11.

Figure 17 Type 9 Connection Diagram

Relay Function

Preset Configuration Setting

 

 

Relay 1 mode

StartStop

Relay 3 mode

Shutdown Bypass

 

 

Gen Run signal hold time

0.5 s

 

 

Preheat time

0 s

 

 

Preheat to crank delay

0 s

 

 

975-0082-01-01

23

Page 33
Image 33
Xantrex Technology 809-0915 manual Type 9 Connection Diagram