Xantrex Technology 809-0915 manual Type, Relay Function Preset Configuration Setting

Models: 809-0915

1 100
Download 100 pages 27.4 Kb
Page 25
Image 25

Xanbus Automatic Generator Start Installation

Type 1

Type 1 is a three-wire GlowStop configuration recommended for “three- wire” generators with glow plugs that need to be operated before a start is attempted.

AGS Harness W ires

Generator W ires

Relay Function

Preset Configuration Setting

 

 

Crank retry time

30 s

 

 

Gen Cool Down

30 s

 

 

Gen Spin Down

3 s

 

 

Shutdown bypass time

0 s

Relay 1

Relay 2

12

13

14

16

17

18

GENERATOR RUN SIGNAL GENERATOR RUN SIGNAL RETURN

5A fuse

PREHEAT/STOP

5A fuse

START

Start tries

3

For additional information, see “Circuit Limitations” on page 11.

Figure 7 Type 1 Connection Diagram

Relay Function

Preset Configuration Setting

 

 

 

 

Relay 1 mode

GlowStop

 

Relay 3 mode

No function

 

 

 

 

Gen Run signal hold time

0.5 s

 

 

 

 

Preheat time

20 s

 

 

 

 

Preheat to crank delay

1 s

 

 

 

 

Crank time

15 s

 

 

 

 

 

 

 

975-0082-01-01

15

Page 25
Image 25
Xantrex Technology 809-0915 manual Type, Relay Function Preset Configuration Setting