Troubleshooting

Table 6 AGS Warning Messages (Continued)

Table 6 AGS Warning Messages (Continued)

Warning

Message

Self-clearing?

Cause

Action

Number

 

 

 

 

 

 

 

 

 

W209

Gen external

Yes

The generator has

Check the generator’s

 

stop. Start

 

stopped, but not by the

fuel level and

 

gen via its

 

AGS. The generator

mechanical condition,

 

control panel.

 

may have run out of

then start the generator

 

 

 

gas, or may have been

manually (using the

 

 

 

shut off by a switch on

switch or control panel

 

 

 

the generator.

on the generator) to

 

 

 

 

clear the warning.

 

 

 

 

 

W250

The selected

No

You have tried to

Put the system into

 

value failed

 

change the Gen Type

Standby, change the

 

to change.

 

without putting the

Gen Type, then return

 

Try again.

 

system into Standby

the system to Operating

 

 

 

first.

mode.

 

 

 

 

 

 

 

 

You have tried to set the

Ensure that “Max Run

 

 

 

“Exercise Dur” for

Time” is set for longer

 

 

 

longer than “Max Run

than “Exercise Dur.”

 

 

 

Time,” or “Max Run

 

 

 

 

Time” for less than

 

 

 

 

“Exercise Dur.”

 

 

 

 

 

 

W500

Network

Yes

The AGS has lost

Check connection

 

connection

 

communications with

between the AGS and

 

lost. Check

 

the network because of

the network.

 

connections.

 

a faulty connection or

 

 

 

 

electronic signal

 

 

 

 

disruption.

 

 

 

 

 

 

Warning

Message

Self-clearing?

Cause

Action

Number

 

 

 

 

 

 

 

 

 

W501

AGS has

No

The AGS encountered

Acknowledge the

 

fixed

 

an internal memory

warning and reset

 

memory

 

problem upon startup.

configurable settings if

 

problem and

 

To remain operational,

necessary.

 

restored

 

the AGS restored its

 

 

default

 

default settings.

 

 

settings.

 

 

 

 

 

 

 

 

975-0082-01-01

71

Page 81
Image 81
Xantrex Technology 809-0915 manual AGS Warning Messages