Image 34

Xanbus Automatic Generator Start Installation

Type 10

Type 10 is a StartStop mode configuration with no preheat signal or shutdown bypass functionality.

AGS Harness W ires

Generator W ires

Relay Function

Preset Configuration Setting

 

 

Gen Cool Down

30 s

 

 

Gen Spin Down

3 s

 

 

Shutdown bypass time

0 s

Relay 1

Relay 2

12

13

14

16

17

18

GENERATOR RUN SIGNAL GENERATOR RUN SIGNAL RETURN

5A fuse

STOP

5A fuse

START

Start tries

3

For additional information, see “Circuit Limitations” on page 11.

Figure 18 Type 10 Connection Diagram

Relay Function

Preset Configuration Setting

 

 

Relay 1 mode

StartStop

Relay 3 mode

No function

Gen Run signal hold time

0.5 s

Preheat time

0 s

Preheat to crank delay

0 s

Crank time

15 s

Crank retry time

30 s

 

 

24

Xanbus Automatic Generator Start (AGS) Owner’s Guide