Xantrex Technology 809-0915 manual Type 13 Connection Diagram

Models: 809-0915

1 100
Download 100 pages 27.4 Kb
Page 37
Image 37

Xanbus Automatic Generator Start Installation

Type 13

Type 13 is a three-wire PulseStop configuration that uses relay 3 to provide the preheat signal. With this generator type, there will be a delay between the generator turning off and the AGS recognizing that the generator is off.

Relay Function

Preset Configuration Setting

 

 

Preheat time

15 s

 

 

Preheat to crank delay

2 s

AGS Harness W ires

Generator W ires

Crank time

15 s

 

 

Crank retry time

15 s

Relay 1

Relay 2

Relay 3

12

13

14

16

17

18

19

20

 

 

 

 

GENERATOR RUN SIGNAL

 

 

 

 

 

 

 

 

GENERATOR RUN SIGNAL RETURN

 

 

 

5A fuse

 

 

 

STOP/PREHEAT

 

 

 

 

 

 

 

 

 

 

 

5A fuse

START

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5A fuse FUEL PRIME (PREHEAT)

12V GENERATOR BATTERY+

Gen Cool Down

30 s

 

 

Gen Spin Down

3 s

 

 

Shutdown bypass time

0 s

 

 

Start tries

3

For additional information, see “Circuit Limitations” on page 11.

Figure 21 Type 13 Connection Diagram

Relay Function

Preset Configuration Setting

 

 

Relay 1 mode

PulseStop

Relay 3 mode

Preheat

 

 

Gen Run signal hold time

5 s

 

 

975-0082-01-01

27

Page 37
Image 37
Xantrex Technology 809-0915 manual Type 13 Connection Diagram