Xanbus Automatic Generator Start Installation
Type 6
Type 6 is a
AGS Harness W ires |
| Generator W ires | |
| 12 |
| GENERATOR RUN SIGNAL |
| 13 |
| GENERATOR RUN SIGNAL RETURN |
| 14 | 5A fuse | PREHEAT |
Relay 1 | 15 | 5A fuse | STOP |
16 |
|
| |
|
|
| |
Relay 2 | 17 | 5A fuse | START |
18 |
|
| |
|
|
|
Relay Function | Preset Configuration Setting |
|
|
Crank retry time | 30 s |
Gen Cool Down | 30 s |
|
|
Gen Spin Down | 3 s |
|
|
Shutdown bypass time | 0 s |
|
|
Start tries | 3 |
|
|
For additional information, see “Circuit Limitations” on page 11.
Figure 12 Type 6 Connection Diagram
Relay Function | Preset Configuration Setting |
|
|
|
|
Relay 1 mode | GlowStop |
|
Relay 3 mode | No function |
|
|
|
|
Gen Run signal hold time | 0.5 s |
|
|
|
|
Preheat time | 10 s |
|
|
|
|
Preheat to crank delay | 1 s |
|
|
|
|
Crank time | 15 s |
|
|
|
|
|
|
|
20 | Xanbus Automatic Generator Start (AGS) Owner’s Guide |