3.1.7 Infrared checklist

Check the following before using infrared communications.

Infrared transmitter (Cable or Pocket PC)

-The Infrared transmitter is pointed directly at the process instrument’s Infrared port.

-The Infrared transmitter is located no more than 0.3 meters (1 foot) away from the process instrument.

Process instrument:

-The process instrument is configured with an Infrared port (Infrared on the UDC2500 is optional; Non Infrared units can be configured using the test jack port, RS485 or Ethernet).

-The process instrument’s device address must match the device address in the P.I.E. Communications Setup.

-The process instrument’s Infrared port must be enabled through its communications menu.

-Any button must be pressed on the process instrument to enable the Infrared port for 4 minutes.

-There are no obstructions between the Infrared transmitter and the process instrument.

P.I.E.:

-There is only one process instrument with the device address selected in the P.I.E. Communication Setup.

-The communications mode in the P.I.E. application must be set to Infrared. (Verify by looking at mode displayed in lower left corner of P.I.E. display.)

Pocket PC:

-IMPORTANT: The beam checkbox in the Pocket PC must be unchecked. See Start\Settings\Connection\Beam. Infrared communications will not work if box is checked.

-A valid IR port address has been assigned through the Infrared Communications Setup screen.

-Dell X5 Pocket PCs require a patch from the Dell website.

-Dell X3 Pocket PCs may require a patch from the Dell website.

16

Process Instrument Explorer Configuration Software User Manual

03/06

Image 22
Contents Process Instrument Explorer Configuration Software Industrial Measurement and Control Abstract ContactsContents Tables Figures Introduction FeaturesOverview Introduction Installation System RequirementsInstall/Upgrade Procedure Select VersionInstallation/upgrade is finished Uninstall Procedure Retain Database?Operations Operations Icons Operations Menu Communications Setup Upload Offline Configuration Arp-d command at a DOS promptDownload Beam at the instrument, then click StartOnline Configuration Maintenance Data Infrared checklist Infrared transmitter Cable or Pocket PCEthernet Q&A How can I find the address of my Honeywell instrument?Pocket PC Services Menu ServicesPC Services Menu Service menu Export Configuration PC only Transfer ConfigurationManage Configuration Files Install Descriptive File PC onlyTransfer Descriptive File PC only Enable Descriptive Name SupportTransfer Healthwatch Data Pocket PC only, UDC3500 only Import Database Import list10Export Database Index Sales and Service Argentina03/06 Industrial Measurement and Control