38VYX110/38VYX130 |
|
Heat pump split system outdoor units |
|
For operation and maintenance instructions of this unit as well as installation |
|
instructions of the indoor unit, refer to the relevant manuals. |
|
Contents |
|
| Page |
Precautions for safety | 2 |
Accessory and refrigerant | 3 |
Selection of installation | 3/4 |
Refrigerant piping | 5 |
Evacuating | 9/10 |
Electrical connections | 10 |
Final installation checks | 11/12 |
ATTENTION INSTALLERS AND SERVICE TECHNICIANS!
AIR CONDITIONER WITH
•
•
•
•
•A vacuum pump is not enough to remove moisture from oil.
•Oils absorb moisture rapidly. Do not expose oil to atmosphere.
•Never open system to atmosphere while it is under vacuum.
•When the system must be opened for service, break vacuum with dry nitrogen.
•Do not vent
•Use only Carrier matching indoor units (Table I).
Table I
Heat | Cassette | Satellite | Power |
|
pump |
| |||
“40KQV” | “40SQV” | supply |
| |
models |
| |||
|
|
|
| |
|
|
|
|
|
38VYX 110 | 110 | 110 |
|
|
38VYX 130 | 130 | 130 | 220⎟ 240V ~ 50Hz |
|
— | — | — |
|
|
— | — | — |
|
|
|
|
|
|
|
|
|
|
|
|