XVI. Supplemental Instructions for Magnetic Motor Starters with

Oneida Air Systems Dust Collectors

Please see complete manufacturer instructions for more information.

This supplement is designed to aid Oneida Air Systems customers with frequently asked questions.

You must have this product installed by a qualified and licensed electrician.

Improper installation is very dangerous and will void your warranty. Follow all local & national electrical codes when installing this product.

This starter can be used in single or 3 phase applications. When used in 1 phase it requires a jumper wire that connects T2 and L3. (See attached wiring diagram.) This “tricks” the overload into thinking it has 3 phase power. This jumper must be installed by a licensed electrician. The jumper is not required if you are using 3 phase power.

Important!

The gauge of the Jumper wire must match the gauge of the wire bringing power to the motor thru the Starter.

Remove the blank plate and install the start / stop pushbutton into the starter cover.

You must mount the Overload Protector to the contactor. The Overload comes in the small white box. It mounts to the three terminals at the bottom of the contactor. See the complete instructions for more information.

Start / Stop Pushbutton

After mounting the overload, connect (2) brown wires marked 95 & 96 to their respective numbered terminals on the overload.

21

10 HP Pulley Drive Owner’s Manual c O.A.S. 2007

Image 22
Contents HP NYB Pulley/Belt Drive Cyclonic Dust Collectors Table of Contents System Start-Up Information II hp Pulley Drive Configurations No Filter Vent OutsideSystem Packages Include 10hp Fan CurvesCyclone C-3500 Optional Items Filter MediaIV. Dimensions External Tube Filters IV. Dimensions External Cartridge Filters 29 1/8Cyclone Stand w/ 55 Gal. Drum STZ350055 Configuration Examples VI. General Assembly Instructions Hole in ring if needed for your orientationSet up Fan/Blower VII. External Filter Bag Assembly OAS Galvanized Plenum BoxXII. Fan / Blower Wiring Diagram Wiring should always be done by a licensed electricianIX. Fan / Blower Maintenance Maintenance of Fan / BlowerMaintenance of Fan / Blower Belt DriveAccessories Multiple DrumsPoor Dust Pick-Up at Woodworking Machines XII. TroubleshootingMotor Overheating Filters filling with large chips and excessive dustXII. Fire Hazards Read Before Installing and Operating Checking in Order Limited WarrantyXIII. Terms and Conditions Delivery Risk of LossXIV. Directions for Cleaning External Filter External Filter can be cleaned using the following methodsMounting Instructions Air Flow to FilterStart / Stop Pushbutton Overload Amperage Dial NEC Nfpa