Carrier 50HCQA Units without Thru-Base Connections, Field Control Wiring, Thermostat

Page 14

50HCQA

LOW VOLTAGE

CONDUIT

CONNECTOR

HIGH VOLTAGE

CONDUIT

CONNECTOR

C08637

Fig. 20 - Thru-Base Connection Fittings

Field-supplied and field-installed liquid-tight conduit connectors and conduit may be attached to the connectors on the basepan. Pull correctly rated high voltage and low voltage through appropriate conduits. Connect the power conduit to the internal disconnect (if unit is so equipped) or to the external disconnect (through unit side panel). A

electronic thermostat, configure it for “non-heat pump” operation. Locate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions.

If the thermostat contains a logic circuit requiring 24-v power, use a thermostat cable or equivalent single leads of different colors with minimum of seven leads. If the thermostat does not require a 24-v source (no “C” connection required), use a thermostat cable or equivalent with minimum of six leads. Check the thermostat installation instructions for additional features which might require additional conductors in the cable.

For wire runs up to 50 ft. (15 m), use no. 18 AWG (American Wire Gage) insulated wire (35_C minimum). For 50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated wire (35_C minimum). For over 75 ft. (23 m), use no. 14 AWG insulated wire (35_C minimum). All wire sizes larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

hole must be field cut in the main control box bottom on the left side so the 24-v control connections can be made. Connect the control power conduit to the unit control box at this hole.

Units without Thru-Base Connections —

1.Install power wiring conduit through side panel open- ings. Install conduit between disconnect and control box.

2.Install power lines to terminal connections as shown in Fig. 16.

All Units: Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. See Table 10. On 3-phase units, voltages between phases must be balanced within 2% and the

Typical

Thermostat

Connections

C

G

W2

(Note 2)

W1

O/B/Y2

(Note 1)

Y1

Central

Terminal

Board

X

C

T

GH E

W2

R

M

 

 

 

O

W1

S

 

 

 

T

Y2

A

 

T

Y1

 

 

 

current within 10%. Use the formula shown in the legend for Table 10, Note 2 (see page 42) to determine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.

Field Control Wiring —

The 50HCQA unit requires an external temperature control device. This device can be a thermostat (field-supplied) or a PremierLink controller (available as factory-installed option or as field-installed accessory, for use on a Carrier Comfort Network or as a stand alone control) or the RTU-MP Controller for Building Management Systems using non-CCN protocols (RTU-MP is available as a factory-installed option only).

Thermostat —

Install a Carrier-approved accessory 2 stage Cooling/Heating thermostat according to installation instructions included with the accessory. The 50HCQ models do not require a thermostat with an O function to control the reversing valve operation. If using an

R

R

Note 1: Typical multi-function marking. Follow manufacturer’s configuration instructions to select Y2. Do not configure for O output.

Note 2: W2 connection not required on units without electric heating.

Field Wiring

C09012

Fig. 21 - Typical Low-Voltage Control Connections

Unit without Thru-Base Connection Kit —

Pass the thermostat control wires through the hole provided in the corner post; then feed the wires through the raceway built into the corner post to the control box. Pull the wires over to the terminal strip on the upper-left corner of the Central Terminal Board (CTB). See Fig. 22.

NOTE: If thru-the-bottom connections accessory is used, refer to the accessory installation instructions for information on routing power and control wiring.

Heat Anticipator Settings —

Set heat anticipator settings at 0.14 amp for the first stage and 0.14 amp for second-stage heating, when available.

14

Image 14
Contents Installation Instructions Safety Considerations Unit Dimensional Drawing 04 06 Size Units Unit Dimensional Drawing 04 06 Size Unit Plan for Unit LocationProvide Unit Support Plan for Sequence of Unit InstallationInspect unit Roof Curb Details Rig and Place Unit For Units with Accessory Electric HeatersField Fabricate Ductwork Convert to Horizontal and Connect Ductwork when required Rigging Details Positioning on CurbInstall Outside Air Hood Economizer Hood Removal and Setup Factory OptionInstall External Condensate Trap and Line Economizer Hood and Two-Position HoodField Power Supply Make Electrical ConnectionsUnits with Factory-Installed Disconnect Convenience OutletsWeatherproof Cover Installation Factory-Option Thru-Base ConnectionsUnits without Thru-Base Connections Field Control WiringHeat Anticipator Settings ThermostatField Control Wiring Raceway Heater Model NumberTypical Module Installation Single Point Boxes and Supplementary FuseSupply Air Temperature SAT Sensor PremierLink ControllerTypical PremierLink Wiring Schematic Field Connections Outdoor Air Temperature OAT SensorSpace Temperature SPT Sensors EconoMi$ert2Space Thermostat Connections PremierLink Sensor Usage Space Sensor Mode Thermostat ModeEconomizer Controls Indoor CO2 Sensor 33ZCSENCO2 Connections Power Exhaust output Filter Status SwitchSupply Fan Status Switch Space Relative Humidity SensorConnecting CCN bus Color Code Recommendations Recommended CablesRTU-MP Control System Typical RTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Type of I/O Connection PIN Name Numbers InputsSpace Temperature Sensor Typical Wiring 33ZCT59SPT Connecting Discrete Inputs RTU-MP / Outdoor CO2 Sensor 33ZCSENCO2 ConnectionsCommunication Wiring Protocols GeneralLocal Access RTU-MP TroubleshootingSystem LEDsLEDs on the RTU-MP show the status of certain functions ControllerSmoke Detector Locations Supply AirAdditional Application Data See Completing Installation of Return Air SmokeCompleting Installation of Return Air Smoke Sensor Unit Wire/Fuse or Hacr Breaker Sizing Data STDUnit No P.E 208/230 208/230---3 STD Smoke Detectors Adjust Factory-Installed OptionsEconoMi$er IV Occupancy Switch Install Accessories Pre-Start and Start-UpCatalog No 50HCQ---01SI

50HCQA specifications

The Carrier 50HCQA is a cutting-edge rooftop air conditioning unit designed for commercial applications, combining efficiency, reliability, and advanced technology to ensure optimal indoor climate control. This model stands out in Carrier's extensive range of HVAC solutions, showcasing a blend of innovative features suitable for diverse building types.

One of the key features of the Carrier 50HCQA is its high-efficiency compressor. With variable-speed capabilities, the compressor adjusts its output to meet the precise cooling or heating demands of the space, promoting energy savings and consistent temperature management. This flexibility results in reduced energy consumption, making the 50HCQA an environmentally friendly choice for businesses looking to lower their carbon footprint.

The 50HCQA integrates advanced microprocessor controls, streamlining operation and enhancing user interaction. This technology allows for sophisticated diagnostics, monitoring, and scheduling, giving facility managers the tools they need to optimize system performance. The user-friendly interface ensures that settings can be easily adjusted, and real-time performance metrics can be accessed to ensure efficient operation.

In terms of construction, the Carrier 50HCQA is built with durability in mind. The unit features a robust cabinet design with a galvanized steel construction that is resistant to corrosion. This feature enhances the longevity of the unit, making it suitable for a variety of weather conditions. Additionally, the insulated casing reduces sound levels, providing a quieter operation that is particularly beneficial in noise-sensitive environments.

Another significant characteristic of the 50HCQA is its environmentally responsible refrigerant options. It utilizes R-410A refrigerant, which has a lower Global Warming Potential (GWP) compared to traditional refrigerants. This aspect not only meets regulatory standards but also supports users in making eco-friendly choices in their HVAC systems.

The 50HCQA also supports a range of optional accessories, including economizers for enhanced energy efficiency and improved air quality. This allows for increased outdoor air intake during suitable conditions, which can significantly contribute to enhancing indoor air quality—an essential factor for occupant comfort and health.

In conclusion, the Carrier 50HCQA is an exemplary model in the commercial HVAC sector, delivering powerful performance, advanced control technologies, and robust construction. Its energy-efficient design, user-friendly controls, and eco-conscious refrigerant options make it a top choice for businesses aiming to invest in sustainable and reliable climate control solutions.