Carrier 50HCQA installation instructions Indoor CO2 Sensor 33ZCSENCO2 Connections

Page 23

H G 24 VAC OR

+ - 24 VDC

+ 0-10VDC

- SIG COM + 4-20mA

NC }ALARM

COM RELAY

NO CONTACTS

2 1 8 7 6 5 4 3 2 1

J3 J4

C08635

Refer to Form 33CS-58SI, PremierLink Installation, Start-up, and Configuration Instructions, for detailed configuration information

Outdoor Air Quality Sensor

(PNO 33ZCSENCO2 plus weatherproof enclosure) —

The outdoor air CO2 sensor is designed to monitor carbon dioxide (CO2) levels in the outside ventilation air and interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged with an outdoor cover. See Fig. 40. The outdoor air CO2 sensor must be located in the economizer outside air hood.

50HCQA

Fig. 38 - Indoor/Outdoor Air Quality (CO2) Sensor

(33ZCSENCO2) - Typical Wiring Diagram

To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return-air grille (if present) so it senses the concentration of CO2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact.

Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.

Wiring the Indoor Air Quality Sensor: For each sensor, use two 2-conductor 18 AWG (American Wire Gage) twisted-pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 38. Connect the 4-20 mA terminal to terminal TB1-9 and connect the SIG COM terminal to terminal TB1-11. See Fig. 39.

IAQ Sensor

TB1PL SEN 9 J5-5

TB1

COM 11 J5-3

24 VAC

C08636

Fig. 39 - Indoor CO2 Sensor (33ZCSENCO2)

Connections

COVER REMOVED

SIDE VIEW

C07135

Fig. 40 - Outdoor Air Quality Sensor Cover

Wiring the Outdoor Air CO2 Sensor: A dedicated power supply is required for this sensor. A two-wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 38. Connect the 4 to 20 mA terminal to the TB1-13 terminal of the 50HCQ. Connect the SIG COM terminal to the TB1-11 terminal of the 50HCQA. See Fig. 41.

OAQ Sensor/RH Sensor

TB1PL SEN 13 J5-2

TB1

COM 11 J5-3

24 VAC

C08275

Fig. 41 - Outdoor CO2 Sensor Connections

Smoke Detector/Fire Shutdown (FSD) —

This function is available only when PremierLink is configured for (Space) Sensor Mode. The unit is factory-wired for PremierLink FSD operation when PremierLink is factory-installed.

23

Image 23
Contents Installation Instructions Safety Considerations Unit Dimensional Drawing 04 06 Size Units Plan for Unit Location Unit Dimensional Drawing 04 06 Size UnitProvide Unit Support Plan for Sequence of Unit InstallationInspect unit Roof Curb Details Rig and Place Unit For Units with Accessory Electric HeatersField Fabricate Ductwork Rigging Details Positioning on Curb Convert to Horizontal and Connect Ductwork when requiredEconomizer Hood Removal and Setup Factory Option Install Outside Air HoodEconomizer Hood and Two-Position Hood Install External Condensate Trap and LineMake Electrical Connections Field Power SupplyConvenience Outlets Units with Factory-Installed DisconnectFactory-Option Thru-Base Connections Weatherproof Cover InstallationThermostat Field Control WiringHeat Anticipator Settings Units without Thru-Base ConnectionsHeater Model Number Field Control Wiring RacewaySingle Point Boxes and Supplementary Fuse Typical Module InstallationPremierLink Controller Supply Air Temperature SAT SensorTypical PremierLink Wiring Schematic EconoMi$ert2 Outdoor Air Temperature OAT SensorSpace Temperature SPT Sensors Field ConnectionsSpace Thermostat Connections PremierLink Sensor Usage Thermostat Mode Space Sensor ModeEconomizer Controls Indoor CO2 Sensor 33ZCSENCO2 Connections Space Relative Humidity Sensor Filter Status SwitchSupply Fan Status Switch Power Exhaust outputRecommended Cables Connecting CCN bus Color Code RecommendationsRTU-MP Control System Typical RTU-MP System Control Wiring Diagram Type of I/O Connection PIN Name Numbers Inputs RTU-MP Controller Inputs and OutputsSpace Temperature Sensor Typical Wiring 33ZCT59SPT RTU-MP / Outdoor CO2 Sensor 33ZCSENCO2 Connections Connecting Discrete InputsGeneral Communication Wiring ProtocolsRTU-MP Troubleshooting Local AccessController LEDsLEDs on the RTU-MP show the status of certain functions SystemSupply Air Smoke Detector LocationsAdditional Application Data See Completing Installation of Return Air SmokeCompleting Installation of Return Air Smoke Sensor STD Unit Wire/Fuse or Hacr Breaker Sizing DataUnit No P.E 208/230 208/230---3 STD Smoke Detectors Adjust Factory-Installed OptionsEconoMi$er IV Occupancy Switch Pre-Start and Start-Up Install AccessoriesCatalog No 50HCQ---01SI

50HCQA specifications

The Carrier 50HCQA is a cutting-edge rooftop air conditioning unit designed for commercial applications, combining efficiency, reliability, and advanced technology to ensure optimal indoor climate control. This model stands out in Carrier's extensive range of HVAC solutions, showcasing a blend of innovative features suitable for diverse building types.

One of the key features of the Carrier 50HCQA is its high-efficiency compressor. With variable-speed capabilities, the compressor adjusts its output to meet the precise cooling or heating demands of the space, promoting energy savings and consistent temperature management. This flexibility results in reduced energy consumption, making the 50HCQA an environmentally friendly choice for businesses looking to lower their carbon footprint.

The 50HCQA integrates advanced microprocessor controls, streamlining operation and enhancing user interaction. This technology allows for sophisticated diagnostics, monitoring, and scheduling, giving facility managers the tools they need to optimize system performance. The user-friendly interface ensures that settings can be easily adjusted, and real-time performance metrics can be accessed to ensure efficient operation.

In terms of construction, the Carrier 50HCQA is built with durability in mind. The unit features a robust cabinet design with a galvanized steel construction that is resistant to corrosion. This feature enhances the longevity of the unit, making it suitable for a variety of weather conditions. Additionally, the insulated casing reduces sound levels, providing a quieter operation that is particularly beneficial in noise-sensitive environments.

Another significant characteristic of the 50HCQA is its environmentally responsible refrigerant options. It utilizes R-410A refrigerant, which has a lower Global Warming Potential (GWP) compared to traditional refrigerants. This aspect not only meets regulatory standards but also supports users in making eco-friendly choices in their HVAC systems.

The 50HCQA also supports a range of optional accessories, including economizers for enhanced energy efficiency and improved air quality. This allows for increased outdoor air intake during suitable conditions, which can significantly contribute to enhancing indoor air quality—an essential factor for occupant comfort and health.

In conclusion, the Carrier 50HCQA is an exemplary model in the commercial HVAC sector, delivering powerful performance, advanced control technologies, and robust construction. Its energy-efficient design, user-friendly controls, and eco-conscious refrigerant options make it a top choice for businesses aiming to invest in sustainable and reliable climate control solutions.