Carrier 50HCQA Plan for Sequence of Unit Installation, Inspect unit, Provide Unit Support

Page 5

Roof Mount —

Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.

Step 2 — Plan for Sequence of Unit Installation

The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb-mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.

Curb-mounted installation —

Install curb

Install field-fabricated ductwork inside curb

Install accessory thru-base service connection package (affects curb and unit) (refer to accessory installation instructions for details)

Prepare bottom condensate drain connection to suit planned condensate line routing (refer to Step 9 for details)

Rig and place unit Install outdoor air hood

Install condensate line trap and piping Make electrical connections

Install other accessories

Pad-mounted installation —

Prepare pad and unit supports

Check and tighten the bottom condensate drain connection plug

Rig and place unit

Convert unit to side duct connection arrangement Install field-fabricated ductwork at unit duct openings Install outdoor air hood

Install condensate line trap and piping Make electrical connections

Install other accessories

Frame-mounted installation —

Frame-mounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan.

Step 3 — Inspect unit

Inspect unit for transportation damage. File any claim with transportation agency.

Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.

Step 4 — Provide Unit Support

Roof Curb Mount —

Accessory roof curb details and dimensions are shown in Fig. 3. Assemble and install accessory roof curb in accordance with instructions shipped with the curb.

NOTE: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 3. Improperly applied gasket can also result in air leaks and poor unit performance.

Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are show in Fig. 4. Refer to Accessory Roof Curb Installation Instructions for additional information as required.

Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and not to the unit. The accessory thru-the-base power package must be installed before the unit is set on the roof curb.

If electric and control wiring is to be routed through the basepan, attach the accessory thru-the-base service connections to the basepan in accordance with the accessory installation instructions.

Slab Mount (Horizontal Units Only) —

Provide a level concrete slab that extends a minimum of

6in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.

NOTE: Horizontal units may be installed on a roof curb if required.

Alternate Unit Support (In Lieu of Curb or Slab Mount) —

A non-combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. (102 mm x 102 mm) pads on each side.

50HCQA

Table 1 – Operating Weights

50HCQA

 

 

UNITS LB (KG)

 

 

 

 

 

 

Component

04

05

06

 

 

 

 

 

 

 

Base Unit

495

(225)

580

(263)

610

(277)

 

 

 

 

 

 

 

Economizer

 

 

 

 

 

 

Vertical

80

(36)

80

(36)

80

(36)

Horizontal

105 (48)

105 (48)

105 (48)

 

 

 

 

 

 

 

Powered Outlet

32

(15)

32

(15)

32

(15)

 

 

 

 

 

 

 

Curb

 

 

 

 

 

 

14--- in / 356 mm

110 (50)

110 (50)

110 (50)

24--- in / 610 mm

145 (66)

145 (66)

145 (66)

5

Image 5
Contents Installation Instructions Safety Considerations Unit Dimensional Drawing 04 06 Size Units Plan for Unit Location Unit Dimensional Drawing 04 06 Size UnitProvide Unit Support Plan for Sequence of Unit InstallationInspect unit Roof Curb Details Rig and Place Unit For Units with Accessory Electric HeatersField Fabricate Ductwork Rigging Details Positioning on Curb Convert to Horizontal and Connect Ductwork when requiredEconomizer Hood Removal and Setup Factory Option Install Outside Air HoodEconomizer Hood and Two-Position Hood Install External Condensate Trap and LineMake Electrical Connections Field Power SupplyConvenience Outlets Units with Factory-Installed DisconnectFactory-Option Thru-Base Connections Weatherproof Cover InstallationHeat Anticipator Settings Field Control WiringUnits without Thru-Base Connections ThermostatHeater Model Number Field Control Wiring RacewaySingle Point Boxes and Supplementary Fuse Typical Module InstallationPremierLink Controller Supply Air Temperature SAT SensorTypical PremierLink Wiring Schematic Space Temperature SPT Sensors Outdoor Air Temperature OAT SensorField Connections EconoMi$ert2Space Thermostat Connections PremierLink Sensor Usage Thermostat Mode Space Sensor ModeEconomizer Controls Indoor CO2 Sensor 33ZCSENCO2 Connections Supply Fan Status Switch Filter Status SwitchPower Exhaust output Space Relative Humidity SensorRecommended Cables Connecting CCN bus Color Code RecommendationsRTU-MP Control System Typical RTU-MP System Control Wiring Diagram Type of I/O Connection PIN Name Numbers Inputs RTU-MP Controller Inputs and OutputsSpace Temperature Sensor Typical Wiring 33ZCT59SPT RTU-MP / Outdoor CO2 Sensor 33ZCSENCO2 Connections Connecting Discrete InputsGeneral Communication Wiring ProtocolsRTU-MP Troubleshooting Local AccessLEDs on the RTU-MP show the status of certain functions LEDsSystem ControllerSupply Air Smoke Detector LocationsAdditional Application Data See Completing Installation of Return Air SmokeCompleting Installation of Return Air Smoke Sensor STD Unit Wire/Fuse or Hacr Breaker Sizing DataUnit No P.E 208/230 208/230---3 STD Smoke Detectors Adjust Factory-Installed OptionsEconoMi$er IV Occupancy Switch Pre-Start and Start-Up Install AccessoriesCatalog No 50HCQ---01SI

50HCQA specifications

The Carrier 50HCQA is a cutting-edge rooftop air conditioning unit designed for commercial applications, combining efficiency, reliability, and advanced technology to ensure optimal indoor climate control. This model stands out in Carrier's extensive range of HVAC solutions, showcasing a blend of innovative features suitable for diverse building types.

One of the key features of the Carrier 50HCQA is its high-efficiency compressor. With variable-speed capabilities, the compressor adjusts its output to meet the precise cooling or heating demands of the space, promoting energy savings and consistent temperature management. This flexibility results in reduced energy consumption, making the 50HCQA an environmentally friendly choice for businesses looking to lower their carbon footprint.

The 50HCQA integrates advanced microprocessor controls, streamlining operation and enhancing user interaction. This technology allows for sophisticated diagnostics, monitoring, and scheduling, giving facility managers the tools they need to optimize system performance. The user-friendly interface ensures that settings can be easily adjusted, and real-time performance metrics can be accessed to ensure efficient operation.

In terms of construction, the Carrier 50HCQA is built with durability in mind. The unit features a robust cabinet design with a galvanized steel construction that is resistant to corrosion. This feature enhances the longevity of the unit, making it suitable for a variety of weather conditions. Additionally, the insulated casing reduces sound levels, providing a quieter operation that is particularly beneficial in noise-sensitive environments.

Another significant characteristic of the 50HCQA is its environmentally responsible refrigerant options. It utilizes R-410A refrigerant, which has a lower Global Warming Potential (GWP) compared to traditional refrigerants. This aspect not only meets regulatory standards but also supports users in making eco-friendly choices in their HVAC systems.

The 50HCQA also supports a range of optional accessories, including economizers for enhanced energy efficiency and improved air quality. This allows for increased outdoor air intake during suitable conditions, which can significantly contribute to enhancing indoor air quality—an essential factor for occupant comfort and health.

In conclusion, the Carrier 50HCQA is an exemplary model in the commercial HVAC sector, delivering powerful performance, advanced control technologies, and robust construction. Its energy-efficient design, user-friendly controls, and eco-conscious refrigerant options make it a top choice for businesses aiming to invest in sustainable and reliable climate control solutions.