Carrier 50HCQA installation instructions Make Electrical Connections, Field Power Supply

Page 11

MINIMUM PITCH

1” (25mm) PER

10’ (3m) OF LINE

TO ROOF

DRAIN

BASE RAIL

2˝ (51) MIN

OPEN

VENT

SEE NOTE

ROOF

CURB

DRAIN PLUG

unit disconnect. On a unit without a unit-mounted disconnect, connect the source leads to compressor contactor C and indoor fan contactor IFC pressure lugs with unit field power leads.

All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the control transformer must be rewired by moving the black wire with the 1/4-in. female spade connector from the 230-v connection and moving it to the 208-v1/4-in. male terminal on the primary side of the transformer. Refer to unit label diagram for additional information. Field power wires will be connected line-side pressure lugs on the

NOTE: Trap should be deep enough to offset maximum unit static difference. A 4” (102) trap is recommended.

C08022

Fig. 14 - Condensate Drain Piping Details

All units must have an external trap for condensate drainage. Install a trap at least 4-in. (102 mm) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do not use a pipe size smaller than the unit connection (3/4-in.).

Step 10 — Make Electrical Connections

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.

NOTE: Check all factory and field electrical connections for tightness. Field-supplied wiring shall conform with the limitations of 63_F (33_C) rise.

Field Power Supply —

If equipped with optional Powered Convenience Outlet: The power source leads to the convenience outlet’s transformer primary are not factory connected. Installer must connect these leads according to required operation of the convenience outlet. If an always-energized convenience outlet operation is desired, connect the source leads to the line side of the unit-mounted disconnect. (Check with local codes to ensure this method is acceptable in your area.) If a de-energize via unit disconnect switch operation of the convenience outlet is desired, connect the source leads to the load side of the

power terminal block or at factory-installed option

non-fused disconnect.

 

 

Field power wires are connected to the unit at line-side

50HCQA

pressure lugs on compressor contactor C and indoor fan

 

contactor IFC or terminal board (see wiring diagram label

 

for control box component arrangement) or at

 

factory-installed option non-fused disconnect switch.

 

Max wire size is #2 AWG (copper only). (See Fig. 16)

 

 

 

NOTE: TEST LEADS - Unit may be equipped with

 

short leads (pigtails) on the field line connection points on

 

contactor C or optional disconnect switch. These leads are

 

for factory run-test purposes only; remove and discard

 

before connecting field power wires to unit connection

 

points. Make field power connections directly to line

 

connection pressure lugs only.

 

!WARNING

FIRE HAZARD

Failure to follow this warning could result in intermittent operation or performance satisfaction.

Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.

(See Fig. 15.)

ELECTRIC

DISCONNECT

SWITCH

COPPER

WIRE ONLY

ALUMINUM

WIRE

A93033

Fig. 15 - Disconnect Switch and Unit

Units Without Factory-Installed Disconnect —

When installing units, provide a disconnect switch per NEC (National Electrical Code) of adequate size. Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet.

11

Image 11
Contents Installation Instructions Safety Considerations Unit Dimensional Drawing 04 06 Size Units Plan for Unit Location Unit Dimensional Drawing 04 06 Size UnitProvide Unit Support Plan for Sequence of Unit InstallationInspect unit Roof Curb Details Rig and Place Unit For Units with Accessory Electric HeatersField Fabricate Ductwork Rigging Details Positioning on Curb Convert to Horizontal and Connect Ductwork when requiredEconomizer Hood Removal and Setup Factory Option Install Outside Air HoodEconomizer Hood and Two-Position Hood Install External Condensate Trap and LineMake Electrical Connections Field Power SupplyConvenience Outlets Units with Factory-Installed DisconnectFactory-Option Thru-Base Connections Weatherproof Cover InstallationThermostat Field Control WiringHeat Anticipator Settings Units without Thru-Base ConnectionsHeater Model Number Field Control Wiring RacewaySingle Point Boxes and Supplementary Fuse Typical Module InstallationPremierLink Controller Supply Air Temperature SAT SensorTypical PremierLink Wiring Schematic EconoMi$ert2 Outdoor Air Temperature OAT SensorSpace Temperature SPT Sensors Field ConnectionsSpace Thermostat Connections PremierLink Sensor Usage Thermostat Mode Space Sensor ModeEconomizer Controls Indoor CO2 Sensor 33ZCSENCO2 Connections Space Relative Humidity Sensor Filter Status SwitchSupply Fan Status Switch Power Exhaust outputRecommended Cables Connecting CCN bus Color Code RecommendationsRTU-MP Control System Typical RTU-MP System Control Wiring Diagram Type of I/O Connection PIN Name Numbers Inputs RTU-MP Controller Inputs and OutputsSpace Temperature Sensor Typical Wiring 33ZCT59SPT RTU-MP / Outdoor CO2 Sensor 33ZCSENCO2 Connections Connecting Discrete InputsGeneral Communication Wiring ProtocolsRTU-MP Troubleshooting Local AccessController LEDsLEDs on the RTU-MP show the status of certain functions SystemSupply Air Smoke Detector LocationsAdditional Application Data See Completing Installation of Return Air SmokeCompleting Installation of Return Air Smoke Sensor STD Unit Wire/Fuse or Hacr Breaker Sizing DataUnit No P.E 208/230 208/230---3 STD Smoke Detectors Adjust Factory-Installed OptionsEconoMi$er IV Occupancy Switch Pre-Start and Start-Up Install AccessoriesCatalog No 50HCQ---01SI

50HCQA specifications

The Carrier 50HCQA is a cutting-edge rooftop air conditioning unit designed for commercial applications, combining efficiency, reliability, and advanced technology to ensure optimal indoor climate control. This model stands out in Carrier's extensive range of HVAC solutions, showcasing a blend of innovative features suitable for diverse building types.

One of the key features of the Carrier 50HCQA is its high-efficiency compressor. With variable-speed capabilities, the compressor adjusts its output to meet the precise cooling or heating demands of the space, promoting energy savings and consistent temperature management. This flexibility results in reduced energy consumption, making the 50HCQA an environmentally friendly choice for businesses looking to lower their carbon footprint.

The 50HCQA integrates advanced microprocessor controls, streamlining operation and enhancing user interaction. This technology allows for sophisticated diagnostics, monitoring, and scheduling, giving facility managers the tools they need to optimize system performance. The user-friendly interface ensures that settings can be easily adjusted, and real-time performance metrics can be accessed to ensure efficient operation.

In terms of construction, the Carrier 50HCQA is built with durability in mind. The unit features a robust cabinet design with a galvanized steel construction that is resistant to corrosion. This feature enhances the longevity of the unit, making it suitable for a variety of weather conditions. Additionally, the insulated casing reduces sound levels, providing a quieter operation that is particularly beneficial in noise-sensitive environments.

Another significant characteristic of the 50HCQA is its environmentally responsible refrigerant options. It utilizes R-410A refrigerant, which has a lower Global Warming Potential (GWP) compared to traditional refrigerants. This aspect not only meets regulatory standards but also supports users in making eco-friendly choices in their HVAC systems.

The 50HCQA also supports a range of optional accessories, including economizers for enhanced energy efficiency and improved air quality. This allows for increased outdoor air intake during suitable conditions, which can significantly contribute to enhancing indoor air quality—an essential factor for occupant comfort and health.

In conclusion, the Carrier 50HCQA is an exemplary model in the commercial HVAC sector, delivering powerful performance, advanced control technologies, and robust construction. Its energy-efficient design, user-friendly controls, and eco-conscious refrigerant options make it a top choice for businesses aiming to invest in sustainable and reliable climate control solutions.