Bryant 650A warranty System Design, Matched System

Page 18

System Design

1.Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.

2.Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C).

3.Maximum outdoor operating air temperature for cooling mode is 125°F (51.7°C).

4.Minimum outdoor operating air temperature for heating mode is –30°F (–34.4°C).

5.Maximum outdoor operating air temperature for heating mode is 66°F (18.9°C).

6.For reliable operation, unit should be level in all horizontal planes.

7.Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft, indoor coil below = 150 ft. (See items 8 and 9 following).

8.For interconnecting refrigerant tube lengths greater than 50 ft and/or elevation differences between indoor and outdoor units greater than 20 ft, con- sult Residential Split-System Application Guideline and Service Manual for Air Conditioners and Heat Pumps using Puron Refrigerant.

9.If ANY refrigerant tubing is buried, provide a minimum 6-in. vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36-in. may be buried without further considerations. Buried refrigerant tubing lengths greater than 36 in. are not recommended.

10.Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.

11.Mixmatches of indoor coil capacity more than 1 size larger than outdoor unit capacity (unless so specified) may result in inadequate indoor comfort.

12.Do not apply capillary tube indoor coils to these units.

13.Factory-supplied filter drier must be installed.

MATCHED SYSTEM

HEAT PUMP

VENTILATOR PLUS

ZONE PERFECT PLUS

EQUIPMENT CONTROLLER

HUMIDIFIER

FAN COIL

AIR CLEANER

A98536

—18—

Image 18
Contents 650A 60 Hz Unit Unit Dimensions DimensionsDimensions Minimum MountingRecommended Tube Diameters Metering DeviceSpecifications ElectricalSpecifications Thermostats and Accessories Accessory Usage GuidelineService Alarm Low-Ambient Pressure SwitchOutdoor Air Temperature Sensor Time-Delay RelayCombination Ratings Combination Ratings 650A Balance Point Worksheet 650AN024-A,C,Outdoor Section With FX4ANF030 Indoor Section Evap Condenser Entering AIR Temperatures FDetailed Cooling Capacities EWB650AN036-A,C Outdoor Section With FX4ANF042 Indoor Section Detailed Cooling Capacities650AN030-A,C Outdoor Section With FX4ANF030 Indoor Section CFM EWB650AN042-A,C Outdoor Section With FV4ANF003 Indoor Section 650AN048-A,C Outdoor Section With FV4ANF005 Indoor SectionCapacity Power Section 650AN060-B,C Outdoor Section With FV4ANB006 Indoor SectionIndoor Cooling Section 650AN024-A,C Outdoor Section With FX4ANF030 Indoor Section Indoor Outdoor Coil Entering AIR Temperatures FHeat Pump Heating Performance EDB CFMMBtuh† Pwr Section Size Capacity PowerHeat Pump Heating Performance Size Capacity18.5 17.0 22.9 21.1 27.9 25.4 33.5 29.8 40.2 36.6 48.2 System Design Matched SystemPage Service Training Call for Free Catalog