Liebert SL-14050 Blower Packs, See Figure #6 for mounting clearances

Page 4

to clearances required for plumbing, electrical, and control entrances. The clearance dimensions shown in this manual are for reference only and are the minimum required for maintenance of the humidifier. Local and National Codes should be consulted prior to final location and installation of the humidifier. Liebert can not accept responsibility for installation code violations.

1.

Location of the humidifier should be below and

 

as close as possible to the steam distributor

 

location as possible.

2.

For front and side clearance requirements (for

 

access during installation, maintenance and

 

troubleshooting), see Figure #2.

3.

If possible, DO NOT locate humidifier any

 

further than absolutely necessary from steam

 

distributor location, as net output will be

 

reduced as a result of heat loss through steam

 

hose. Also, increased static pressure may

 

cause operational problems and necessitate

 

use of the fill cup extension kit and other

 

components.

4.

Where possible, mount humidifier at a height

 

convenient for servicing.

In addition, install a minimum of 2 field supplied fasteners in the holes provided in the back of the unit to prevent the unit from being bumped off the wall bracket.

6.Make sure humidifier is level.

7.DO NOT mount humidifier on hot surfaces.

8.If humidifiers are mounted on roof, a thermostatically ventilated weatherproof cabinet by others should be used. Consult factory.

9.DO NOT mount humidifiers in an area where freezing may occur.

10.DO NOT mount humidifiers on vibrating surface.

BLOWER PACKS

1.Blower packs are an optional accessory used to directly distribute steam to localized areas (such as computer rooms) or in structures that do not have a built-in air distribution system.

Figure #4

Built On Blower Pack

5. Wall mounting bracket provided should be

securely attached horizontally and open edge

upwards, using field-supplied fasteners. Use

a minimum of 3 - #12 x 3" long wood screws,

or better, into a vertical structural surface. If

any spacer material is used between the

bracket and the structural material such as

drywall, increase fastener length accordingly.

Figure #3

Wall Bracket Mounting Detail

Optional

Built-On

Blower Pack

Single

Circuit

Humidifier

Built-In

Supply Air

Grille

Built-In Steam Distributor

WALL

 

 

7.7”

FASTENWALL BRACKET

A

(19.6 cm)

(FACTORYSUPPLIED)TO

 

WALL USING ANCHOR BOLTS

 

(3) SUPPLIEDBY OTHERS

 

005-030 050-200

A 7.7"(19.6cm) 7.7"(19.6cm)

Power And

Control

Wiring

See Figure #6 for mounting clearances.

2.Blower packs are available integrally-mounted on humidifier (built-on blower pack, BOBP, see Figure #4) or detached and field-piped and wired to humidifier (remote mounted blower pack RMBP, see Figure #5).

- 2 -

Image 4
Contents Installation Operation Guide Table Of Contents PRE-INSTALLATION Checkpoint Basic Humidifier ConfigurationReceiving & Unpacking Equipment Location & MountingBlower Packs See Figure #6 for mounting clearancesFront Side Steam DistributorsFigure #7 Steam Distributor Location Plumbing Water Supply LineDrain Line Steam LineFigure #19 Long Steam Lines Accessories Fill CUP Extension Kits Condensate Return LinePrimary Voltage Supply Wiring to Humidifier LOW Voltage Control WiringElectrical On-Off ControlsOptional Modulation Continuous Control InstallationControls see Figure #28 Manual Capacity Adjustment IntroductionSGH Operation Optional Modulation Continuous Control Packages by LiebertOther Potentiometers Detecting Water Supply DeficiencyRemote Indication Double Unit OperationLimited Warranty Cylinder Last Replaced