Bryant 280ANV Pressure Switch Protection, Control Fault, Brown-Out Protection

Page 13

Pressure Switch Protection

The outdoor unit is equipped with high pressure switch. If the control senses the opening of a high pressure switch, it will respond as follows:

1.De-energize the contactor.

2.Keep the outdoor fan operating for 15 minutes.

3.Display the appropriate fault code (see Table 7).

4.After a 15 minute delay, if there is a call for cooling or heat- ing and HPS is reset, the contactor is energized.

5.If HPS has not closed after a 15 minute delay, the outdoor fan is turned off. If the open switch closes anytime after the 15 minute delay, then resume operation with a call for cool- ing or heating at a temporary reduced capacity.

6.If HPS trips 3 consecutive cycles, the unit operation is locked out for 4 hours.

7.In the event of a high-pressure switch trip or high-pressure lockout, check the refrigerant charge, outdoor fan operation, and outdoor coil (in cooling) for airflow restrictions, or in- door airflow in heating.

8.In the event of a low-pressure trip or low-pressure lockout, check the refrigerant charge and indoor airflow (cooling) and outdoor fan operation and outdoor coil in heating.

Control Fault

If the outdoor unit control board has failed, the control will flash the appropriate fault code (see Table 7). The control board should be replaced.

Brown-Out Protection

If the line voltage is less than 187v for at least 4 seconds, the contactor and fan relay are de-energized. Compressor and fan operation are not allowed until voltage is a minimum of 190v. The control will flash the appropriate fault code (see Table 7).

230V Line (Power Disconnect) Detection

If there is no 230v at the contactor when the indoor unit is powered with a cooling or heating demand, the appropriate fault code is displayed. Verify the disconnect is closed and 230v wiring is connected to the unit.

Inverter Voltage Sensing

The control board senses the presence or absence of 230 V through the feedback from inverter. The control monitors the high voltage to the inverter. Voltage should be present anytime the contactor is energized and voltage should not be present when the contactor is de-energized.

Temperature Thermistors

Thermistors are electronic devices which sense temperature. As the temperature increases, the resistance decreases. Thermistors are used to sense outdoor air (OAT), coil temperature (OCT) and the suction line thermistor (OST) located between the reversing valve and the accumulator.

Refer to Table 4 and Fig. 14 for resistance values versus temperature.

Table 4 – Resistance Values versus Temperature

TEMPERATURE

RESISTANCE (ohms)

 

 

25.0° C (77.0° F)

10.0 + / - 2.3%

 

 

0.0° C (32.0° F)

32.6 + / - 3.2%

 

 

-28.0° C (-18.4° F)

85.5 + / - 3.4%

 

 

THERMISTOR CURVE

 

90

(KOHMS)

80

70

 

60

RESISTANCE

50

20

 

40

 

30

10

0

0

20

40

60

80

100

120

 

 

TEMPERATURE (DEG. F)

 

 

A91431

Fig. 14 - Thermistor Resistance Versus Temperature

If the outdoor air or coil thermistor should fail, the control will flash the appropriate fault code (see Table 7.)

IMPORTANT: The outdoor air thermistor, coil thermistor and suction thermistor should be factory mounted in the final

locations. Check to ensure thermistors are mounted properly (See Fig. 15, 16 and 17).

Thermistor Sensor Comparison

The control continuously monitors and compares the outdoor air temperature sensor and outdoor coil temperature sensor to ensure proper operating conditions. The comparison is:

SIn cooling if the outdoor air sensor indicates 10_F (5.6_C) warmer than the coil sensor (or) the outdoor air sensor indicates

20_F (11_C) cooler than the coil sensor, the sensors are out of range.

SIn heating if the outdoor air sensor indicates 35_F (19.4_C) warmer than the coil sensor (or) the outdoor air sensor indicates 10_F (5.6_C) cooler than the coil sensor, the sensors are out of range.

If the sensors are out of range, the control will flash the appropriate fault code as shown in Table 7.

The thermistor comparisons are not performed during low ambient cooling or defrost operation.

Failed Thermistor Default Operation

Factory defaults have been provided in the event of failure of outdoor air thermistor (OAT) and/or outdoor coil thermistor (OCT).

If the OAT sensor should fail, low ambient cooling will not be allowed and the one-minute outdoor fan off delay will not occur. Defrost will be initiated based on coil temperature and time.

If the OCT sensor should fail, low ambient cooling will not be allowed. Defrost will occur at each time interval during heating operation, but will terminate after 5 minutes.

If there is a thermistor out-of-range error, defrost will occur at each time interval during heating operation, but will terminate after 5 minutes.

Count the number of short and long flashes to determine the appropriate flash code. Table 7 gives possible causes and actions related to each error.

13

Image 13
Contents Table of Contents Installation InstructionsInverter Cover Safety ConsiderationsInstallation Recommendations InstallationCheck Equipment and Job Site Unpack UnitClearance Requirements Install on a Solid, Level Mounting PadOperating Ambient Elevate UnitMake Piping Connections Accessory UsagePersonal Injury and Unit Damage Hazard Unit Damage HazardNo Installation of Adapter Tube Install Liquid-Line Filter Drier IndoorOutdoor Unit Connected to Factory-Approved Indoor Refrigerant Tubing connection OutdoorCompressor Crankcase Heater Make Electrical ConnectionsStart-Up Install AccessoriesSystem Functions And Sequence Of Operation Follow these steps to properly start up the systemDefrost Communication and Status Function LightsHeating Check Chart Procedure Check Charge Charge in Charging modePumpdown & Evacuation Evacuation and Recovery of Refrigerant from within 280ANVPump Down Major Components TroubleshootingControl Fault Pressure Switch Protection230V Line Power Disconnect Detection Temperature ThermistorsOutdoor Coil Thermistor Variable Speed Compressor Power Input TerminalsSuction Thermistor OST Variable Speed Compressor Sensor Output TerminalsExample Status CodesVariable Speed Control Board With optional Utility Relay Hours TroubleshootingFinal Checks Care and MaintenancePuronr R-410A Refrigerant Quick Reference Guide
Related manuals
Manual 4 pages 21.14 Kb

280ANV specifications

The Bryant 280ANV is a highly efficient air conditioning unit designed for residential use, providing homeowners with reliable cooling performance while maintaining energy efficiency. One of the standout features of the Bryant 280ANV is its two-stage compressor, which allows for variable speed operation. This means that the unit can adjust its cooling output to match the current demand for indoor comfort, leading to more consistent temperatures and increased energy savings.

The Bryant 280ANV also boasts an impressive SEER (Seasonal Energy Efficiency Ratio) rating, which indicates its energy efficiency. Typically, this model achieves a SEER rating of up to 20, making it a strong contender in the market for those looking to reduce their energy bills without sacrificing comfort. This level of efficiency not only results in lower monthly costs but also contributes to a reduced environmental footprint.

Another key technology featured in the Bryant 280ANV is its advanced, variable-speed blower motor. This motor helps to operate quietly while ensuring optimal airflow throughout the home. The quiet operation of the 280ANV means that it can deliver cooling without disturbing your daily life, making it an excellent choice for bedrooms or other quiet spaces.

The unit is also designed with durability in mind. Its cabinet is constructed from high-quality, weather-resistant materials that protect against harsh outdoor conditions. This ensures longevity and reliable performance over the years. Furthermore, the Bryant 280ANV includes a protected scroll compressor that adds an extra layer of reliability and enhances the unit's overall efficiency.

Installation of the Bryant 280ANV can be completed by a qualified HVAC professional, who can ensure that the system is set up to operate at peak performance. Additional features, such as the built-in Wi-Fi capability, allow homeowners to connect the unit to smart home systems for enhanced control and convenience.

In conclusion, the Bryant 280ANV combines energy efficiency with advanced technology to provide effective cooling solutions for residential spaces. With its two-stage compressor, high SEER rating, quiet operation, and durable construction, it meets the needs of modern homeowners who value comfort, efficiency, and reliability. Overall, the Bryant 280ANV stands out as a quality choice for those seeking a dependable air conditioning system.