MAJOR COMPONENTS

Variable speed Control Board

The HP control board controls the following functions:

SCompressor speed S Contactor operation

S Outdoor fan motor operation S Reversing valve operation S Defrost operation

S Low ambient cooling

S Crankcase heater operation S Pressure switch monitoring S Time Delays

S Pressure Transducer

S .EXV operation control

S .Inverter communication and control

Inverter

The inverter is located inside the control box. This is an air-cooled device that communicates with the control board and drives the compressor to the demanded RPM. When the contactor closes, it powers the inverter with line voltage. The inverter converts the line voltage to 410 volts DC. The inverter then converts DC voltage into 3-phase variable frequency and variable voltage.

NOTE: Manually closing the contactor will not cause the unit to operate. The unit must be operated with an Evolution Control. A standard thermostat will allow operation only in the emergency mode (high speed heating or cooling).

Motor Control Drive (Inverter):

S Converts the sinusoidal AC input mains voltage into a variable frequency AC output generated used PWM modulation of the output.

SDrive adjusts the output voltage to run the compressor at the correct speed at any load point in the envelope.

SThe drive actively controls the motor current to insure the proper torque is provided for the given loading condition.

SThe drive control algorithms insure the magnetic field set up in

the motor is synchronized with the rotor insuring smooth efficiency operation.

S The drive actively controls the input current at heavy loading conditions to insure the input power factor to the drive is >0.95.

Variable Speed Compressor

This unit contains a variable speed compressor that has a wide operating range. This compressor can only be operated by the specific inverter supplied with the unit.

Motor Control Drive + BPM together:

SThrough the combination of the drive and motor, the system is able to operate over a wide speed range.

SThe drive provides protection of the system to various abnormal conditions including limiting the compressor envelope of operation to appropriate boundaries.

SProvides many pieces of system data as feedback to the system controller.

SAllows operation at least than full performance in case of system faults or issues.

!CAUTION

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage and/or improper operation.

Do not attempt to apply line voltage directly to the compressor. This will destroy the compressor.

Compressor Brush-less Permanent Magnet Motor (BPM):

SThe motor inductance reacts to the drive current and a sinusoidal

current is induced through the motor windings.

S The sinusoidal current sets a rotating magnetic field, at the frequency set by the drive.

SThe magnets enable the motor to synchronize to that frequency, set by the drive.

SSupplies the mechanical power afforded to it by the drive voltage, current and frequency.

Electronic Expansion Valve (EXV)

This unit uses an electronic expansion valve for refrigerant metering in the heating mode. The control board drives the EXV to its proper position based on the operating mode and conditions. The Evolution Control Service mode allows for manual opening and closing of the EXV for troubleshooting and pump down.

Field control Connections

For normal operation use the ABCD Evolution connections only. Only two wires, AB are required. See Fig. 18. Discrete inputs (Y,C,

O)are available for emergency operation if the Evolution Bus is not in operation.

Pressure Transducer (SPT)

A 5 VDC output low pressure transducer that provides a 0-5 VDC data for interpretation by the control board for a 0 to 200 psig range of pressure at the suction tube. This interpreted pressure data is then intelligently used by the control board for low pressure cut-out, loss of charge management, compressor overall envelope management, oil circulation management, lubrication management and EXV control. (See Fig. 17.)

Compressor Control Contactor

The contactor has a 24 volt coil. The electronic control board controls the operation of the contactor.

TROUBLESHOOTING

Systems Communication Failure

If communication with the Evolution control is lost with the User Interface (UI), the control will flash the appropriate fault code (see Table 7). Check the wiring to the User Interface and the indoor and outdoor units and power.

Model Plug

Each control board contains a model plug. The correct model plug must be installed for the system to operate properly (see Table 3).

Table 3 – Model Plug Information

MODEL

 

PIN RESISTANCE

MODEL PLUG

(K---ohms)

NUMBER

NUMBER

 

 

 

 

Pins 1---4

Pins 2---3

 

 

 

 

280ANV024

HK70EZ001

5.1K

11K

 

 

 

 

280ANV036

HK70EZ002

5.1K

18K

 

 

 

 

280ANV048

HK70EZ003

5.1K

24K

 

 

 

 

280ANV060

HK70EZ004

5.1K

33K

 

 

 

 

The model plug is used to identify the type and size of unit to the control.

On new units, the model and serial numbers are input into the board’s memory at the factory. If a model plug is lost or missing at initial installation, the unit will operate according to the information input at the factory and the appropriate error code will flash temporarily. An RCD replacement board contains no model and serial information. If the factory control board fails, the model plug must be transferred from the original board to the replacement board for the unit to operate.

NOTE: The model plug takes priority over factory model information input at the factory. If the model plug is removed after initial power up, the unit will operate according to the last valid model plug installed, and flash the appropriate fault code temporarily.

12

Image 12
Contents Installation Instructions Table of ContentsSafety Considerations Inverter CoverInstallation Installation RecommendationsCheck Equipment and Job Site Unpack UnitInstall on a Solid, Level Mounting Pad Clearance RequirementsOperating Ambient Elevate UnitAccessory Usage Make Piping ConnectionsPersonal Injury and Unit Damage Hazard Unit Damage HazardInstall Liquid-Line Filter Drier Indoor No Installation of Adapter TubeOutdoor Unit Connected to Factory-Approved Indoor Refrigerant Tubing connection OutdoorMake Electrical Connections Compressor Crankcase HeaterInstall Accessories Start-UpSystem Functions And Sequence Of Operation Follow these steps to properly start up the systemCommunication and Status Function Lights DefrostCheck Charge Charge in Charging mode Heating Check Chart ProcedureEvacuation and Recovery of Refrigerant from within 280ANV Pumpdown & EvacuationPump Down Troubleshooting Major ComponentsPressure Switch Protection Control Fault230V Line Power Disconnect Detection Temperature ThermistorsVariable Speed Compressor Power Input Terminals Outdoor Coil ThermistorSuction Thermistor OST Variable Speed Compressor Sensor Output TerminalsStatus Codes ExampleVariable Speed Control Board With optional Utility Relay Troubleshooting HoursCare and Maintenance Final ChecksPuronr R-410A Refrigerant Quick Reference Guide
Related manuals
Manual 4 pages 21.14 Kb

280ANV specifications

The Bryant 280ANV is a highly efficient air conditioning unit designed for residential use, providing homeowners with reliable cooling performance while maintaining energy efficiency. One of the standout features of the Bryant 280ANV is its two-stage compressor, which allows for variable speed operation. This means that the unit can adjust its cooling output to match the current demand for indoor comfort, leading to more consistent temperatures and increased energy savings.

The Bryant 280ANV also boasts an impressive SEER (Seasonal Energy Efficiency Ratio) rating, which indicates its energy efficiency. Typically, this model achieves a SEER rating of up to 20, making it a strong contender in the market for those looking to reduce their energy bills without sacrificing comfort. This level of efficiency not only results in lower monthly costs but also contributes to a reduced environmental footprint.

Another key technology featured in the Bryant 280ANV is its advanced, variable-speed blower motor. This motor helps to operate quietly while ensuring optimal airflow throughout the home. The quiet operation of the 280ANV means that it can deliver cooling without disturbing your daily life, making it an excellent choice for bedrooms or other quiet spaces.

The unit is also designed with durability in mind. Its cabinet is constructed from high-quality, weather-resistant materials that protect against harsh outdoor conditions. This ensures longevity and reliable performance over the years. Furthermore, the Bryant 280ANV includes a protected scroll compressor that adds an extra layer of reliability and enhances the unit's overall efficiency.

Installation of the Bryant 280ANV can be completed by a qualified HVAC professional, who can ensure that the system is set up to operate at peak performance. Additional features, such as the built-in Wi-Fi capability, allow homeowners to connect the unit to smart home systems for enhanced control and convenience.

In conclusion, the Bryant 280ANV combines energy efficiency with advanced technology to provide effective cooling solutions for residential spaces. With its two-stage compressor, high SEER rating, quiet operation, and durable construction, it meets the needs of modern homeowners who value comfort, efficiency, and reliability. Overall, the Bryant 280ANV stands out as a quality choice for those seeking a dependable air conditioning system.