Bryant 286B Check Equipment and Job Site, Install on a Solid, Level Mounting Pad, Elevate Unit

Page 2

286B / 289B

OUTDOOR WALL

INDOOR WALL

CAULK

LIQUID TUBE

 

INSULATION

SUCTION TUBE

 

THROUGH THE WALL

JOIST

HANGER STRAP

(AROUND SUCTION

TUBE ONLY) INSULATION

SUCTION TUBE

1” (25.4 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MIN

 

 

 

 

 

 

 

LIQUID TUBE

 

 

 

 

 

 

 

 

SUSPENSION

A07588

Fig. 1 - Connecting Tubing Installation

Specifications for this unit in residential new construction market require the outdoor unit, indoor unit, refrigerant tubing sets, metering device, and filter drier listed in presale literature. There can be no deviation. Consult the Service Manual – Air Conditioners and Heat Pumps Using Puron® Refrigerant to obtain required unit changes for specific applications and for R-22 retrofit.

Check Equipment and Job Site

Unpack Unit

Move to final location. Remove carton taking care not to damage unit.

Inspect Equipment

File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit corner panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.

Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 2 to determine base pan size and knockout hole location.

For hurricane tie downs, contact distributor for details and PE (Professional Engineer)Certification, if required.

On rooftop applications, mount on level platform or frame. Place unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.

Roof mounted units exposed to winds above 5 mph may require wind baffles. Consult the Service Manual - Residential Split System Air Conditioners and Heat Pumps Using Puron® Refrigerant for wind baffle construction.

NOTE: Unit must be level to within ±2° (±3/8 in./ft,±9.5 mm/m.)per compressor manufacturer specifications.

Clearance Requirements

When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm) clearance to service end of unit and 48 in. (1219.2 mm) (above unit. For proper airflow, a 6-in. (152.4 mm) clearance on 1 side of unit and 12-in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.

On rooftop applications, locate unit at least 6 in. (152.4 mm) above roof surface.

3/8---in. (9.53 mm) Dia. Tiedown Knockouts in Basepan(2) Places

View From Top

UNIT BASE PAN

TIEDOWN KNOCKOUT LOCATIONS in. (mm)

Dimension in. (mm)

A

B

C

35 X 35

9–1/8 (231.8)

6–9/16 (166.7)

28–7/16 (722.3)

(889 X 889)

 

 

 

 

 

 

A05177

Fig. 2 - Tiedown Knockout Locations

Operating Ambient

The minimum outdoor operating ambient in cooling mode is 55_F (12.78_C) without low ambient cooling enabled, and the maximum outdoor operating ambient in cooling mode is 125_F (51.67_C). At line voltage of 208v (or below) and an outdoor ambient of 120_F (48.9_C) (and above), the compressor operates in low stage. On Evolution communicating systems ONLY, low ambient cooling operation is possible at ambient as low as 0_F (-17.78_C).

The maximum outdoor operating ambient in heating mode is 66°F/18.89_C on all models.

Elevate Unit

!CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Do not allow water and/or ice to build up in base pan.

Elevate unit per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of unit.

!CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Locate the unit in such a way that it is stable in all circumstances including adverse weather conditions.

In Long-Line Applications, Install Liquid-Line Solenoid Valve (LSV)

For refrigerant piping arrangements with equivalent lengths greater than 80 ft. (24.38 m) and/or when elevation difference between indoor and outdoor unit is greater than ±20 ft. (±6.10 m), follow all requirements of the Residential Piping and Long-Line Guideline. If required by the Residential Piping and Long-Line Guideline, install LSV kit, part no. KHALS0401LLS, specifically designed for PuronR refrigerant heat pumps. LSV should be installed within 2 ft. (0.61 m) of outdoor unit with flow arrow pointing toward outdoor unit. Follow the Installation Instructions included with accessory kit.

IMPORTANT: Flow arrow must point toward outdoor unit.

2

Image 2
Contents CUT Hazard Installation RecommendationsElectrical Shock Hazard Indoor Thermostat Control OptionsClearance Requirements Install on a Solid, Level Mounting PadCheck Equipment and Job Site Operating AmbientOutdoor Unit Connected to Factory-Approved Indoor Accessory UsageMake Piping Connections Personal Injury and Unit Damage HazardRefrigerant Tubing connection Outdoor Install Liquid-Line Filter Drier IndoorInstall Adapter Tube Sweat ConnectionsAirflow Selections ECM Furnaces- non commu- nicating Make Electrical ConnectionsCompressor Crankcase Heater System Functions And Sequence Of Operation Install AccessoriesStart-Up Follow these steps to properly start up the systemCrankcase Heater Operation Time DelaysCommunication and Status Function Lights Outdoor Fan Motor OperationEvolution Controlled low ambient cooling DefrostCheck Charge 230V Line Power Disconnect Detection Pressure Switch ProtectionControl Fault Field ConnectionsFailed Thermistor Default Operation Unloader Test ProcedureTemperature Thermistors Contactor Shorted DetectionStatus Codes TroubleshootingAmber LED Fault Flash Possible Cause and Action Code Thermidistat Models T6-PRH-01 or T6-NRH-01 Puronr R-410A Refrigerant Quick Reference Guide Care and MaintenanceFinal Checks