Bryant 548J*14D installation instructions Unit Powered Convenience Outlet Wiring

Page 14

548J*14D

the transformer; however, the conduit must be routed so that all wiring is either in the conduit or behind the access panel.

If the convenience outlet transformer is connected to the line side of the factory disconnect option, route the wires through the web bushing located on the bottom of the disconnect box. For the load side wiring to the factory option disconnect, route the wires through the hole on the right side of the disconnect. Be sure to create a drip loop at least 6” long.

Duty Cycle: the unit-powered convenience outlet has a duty cycle limitation. The transformer is intended to provide power on an intermittent basis for service tools, lamps, etc; it is not intended to provide 15-amps loading for continuous duty loads (such as electric heaters for overnight use). Observe a 50% limit on circuit loading above 8-amps (i.e., limit loads exceeding 8-amps to 30 minutes of operation every hour).

Test the GFCI receptacle by pressing the TEST button on the face of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip as required. Press the RESET button to clear the tripped condition.

C08283

UNIT

CONNECT

PRIMARY

TRANSFORMER

VOLTAGE

AS

CONNECTIONS

TERMINALS

 

 

 

 

208,

240

L1: RED +YEL

H1 + H3

230

L2: BLU + GRA

H2 + H4

 

 

 

 

 

 

 

L1: RED

H1

460

480

Splice BLU + YEL

H2 + H3

 

 

L2: GRA

H4

 

 

 

 

575

600

L1: RED

H1

L2: GRA

H2

 

 

 

 

 

 

Fig. 24 - Unit Powered Convenience Outlet Wiring

Fuse on power type: The factory fuse is a Bussman “Fusetron” T-15, non-renewable screw-in (Edison base) type plug fuse.

!WARNING

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury or death.

Using unit-mounted convenience outlets: Units with unit-mounded convenience outlet circuits will often require that two disconnects be opened to de-energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de-energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets.

Installing Weatherproof Cover: A weatherproof while-in-use cover for the factory-installed convenience outlets is now required by UL standards. This cover cannot be factory-mounted due its depth; it must be installed at unit installation. For shipment, the convenience outlet is covered with a blank cover plate.

The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate and gasket.

DISCONNECT ALL POWER TO UNIT AND CONVENIENCE OUTLET.

Remove the blank cover plate at the convenience outlet; discard the blank cover.

Loosen the two screws at the GFCI duplex outlet, until approximately 1/2-in (13 mm) under screw heads are exposed. Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug (do not over-tighten).

Mount the weatherproof cover to the backing plate as shown in Fig. 25. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover. Check for full closing and latching.

COVER – WHILE-IN-USE

RECEPTACLE

WEATHERPROOF

NOT INCLUDED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BASE PLATE FOR

GFCI RECEPTACLE

C09022

Fig. 25 - Weatherproof Cover Installation

14

Image 14
Contents Installation Instructions Safety Considerations Unit Dimensional Drawing Size 14 Unit Service Clearance Dimensional Drawing Plan for Unit LocationProvide Unit Support Plan for Sequence of Unit InstallationInspect Unit Roof Curb Details Rig and Place Unit For Units with Accessory Electric HeatersField Fabricate Ductwork Economizer Hood Removal and Setup Factory Option Convert to Horizontal and Connect Ductwork when requiredInstall Outside Air Hood Positioning on CurbDamper Assembly Install External Condensate Trap and Line Economizer Hood and Two-Position HoodField Power Supply Make Electrical ConnectionsMounting Position for Field Disconnects Over 100A Units Without Factory-Installed Disconnect Units with Factory-Installed DisconnectUnit Powered Convenience Outlet Wiring Thermostat Field Control WiringFactory-Option Thru-Base Connections Units without Thru-Base ConnectionsHeat Anticipator Settings Unit without Thru-Base Connection KitHeater Low-Voltage Control Connections Single Point BoxesHeater and Supplementary Fuses Differential Enthalpy Control Outdoor Air Enthalpy Control PNO 33CSENTHSWReturn Air Enthalpy Sensor RTU-MP Control System RTU-MP System Control Wiring Diagram Supply Air Temperature SAT Sensor RTU-MP Controller Inputs and OutputsField Connections Outdoor Air Temperature OAT SensorSpace Temperature SPT Sensors EconoMi$er2RTU-MP T-56 Sensor Connections Indoor Air Quality CO2 sensorWeatherproof enclosure Connecting Discrete InputsOutdoor Air Quality Sensor PNO 33ZCSENCO2 plus RTU-MP Troubleshooting Communication Wiring ProtocolsLocal Access GeneralLEDs LEDs on the RTU-MP show the status of certain functionsController Smoke DetectorsSystem SensorReturn Air with Economizer Smoke Detector LocationsSupply Air Completing Installation of Return Air Smoke Sensor Return Air Detector Shipping PositionUnit Wire/Fuse or Hacr Breaker Sizing Data NonePwrd C.O Adjust Factory-Installed Options EconoMi$er IV Occupancy SwitchInstall Accessories Pre-Start and Start-Up548J*14D 548J*14D Catalog No. II548J---07

548J*14D specifications

The Bryant 548J*14D is a highly efficient and versatile air conditioning unit designed to meet the varying demands of residential and light commercial applications. This model stands out due to its advanced engineering, energy-saving features, and reliable performance, making it an ideal choice for homeowners looking to enhance comfort without compromising on energy efficiency.

One of the main features of the Bryant 548J*14D is its excellent SEER (Seasonal Energy Efficiency Ratio) rating, which signifies its ability to provide cooling while consuming less energy. Optimized for efficiency, this unit employs a high-efficiency compressor that adjusts its output based on cooling demands, allowing it to use only the energy necessary to maintain a comfortable environment.

The unit’s all-aluminum evaporator coil ensures durability and resistance to corrosion, contributing to its longer lifespan and consistent performance. Additionally, the Bryant 548J*14D incorporates advanced refrigeration technologies for maximum heat transfer efficiency. This technology not only enhances cooling performance but also improves overall system reliability.

A key characteristic of the Bryant 548J*14D is its Whisper Series technology designed for quiet operation. The low-noise design minimizes sound levels, allowing for unobtrusive cooling in residential spaces while still ensuring effective airflow and cooling capacity. This makes it particularly favorable for installation in bedrooms and other noise-sensitive areas.

Another noteworthy aspect of the Bryant 548J*14D is its compatibility with the MyBryant smartphone app, which enables homeowners to monitor and control their HVAC systems remotely. This connectivity offers convenience and helps to optimize energy usage, as users can adjust settings based on their schedules and preferences.

Furthermore, the Bryant 548J*14D is designed with a robustness that allows it to withstand diverse weather conditions, ensuring reliable performance even in extreme climates. The unit’s compact design eases installation in various settings, whether it's on rooftops, near walls, or on concrete pads.

In summary, the Bryant 548J*14D is a cutting-edge air conditioning unit that combines energy efficiency, quiet operation, and advanced technologies. With its robust construction, smart features, and reliable performance, it stands as a valuable solution for anyone looking to enhance comfort and save on energy costs in their homes or light commercial environments.