Bryant 548J*14D RTU-MP Controller Inputs and Outputs, Supply Air Temperature SAT Sensor

Page 21

Table 2 – RTU-MP Controller Inputs and Outputs

 

 

POINT NAME

BACnet OBJECT

 

TYPE OF I/O

CONNECTION PIN

 

 

NAME

 

NUMBERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUTS

 

 

 

 

 

 

 

Space Temperature Sensor

sptsens

 

AI (10K Thermistor)

J20---1, 2

 

 

 

 

 

Supply Air Temperature

sat

 

AI (10K Thermistor)

J2---1, 2

 

 

 

 

 

Local Outside Air Temperature Sensor

oatsens

 

AI (10K Thermistor)

J2---3, 4

 

 

 

 

 

Space Temperature Offset Pot

sptopot

 

AI (100K Potentiometer)

J20---3

 

 

 

 

 

Indoor Air Quality

iaq

 

AI (4---20 ma)

J4---2, 3

 

 

 

 

 

Outdoor Air Quality

oaq

 

AI (4---20 ma)

J4---5, 6

 

 

 

 

 

Safety Chain Feedback

safety

 

DI (24 VAC)

J1---9

 

 

 

 

 

Compressor Safety

compstat

 

DI (24 VAC)

J1---2

 

 

 

 

 

Fire Shutdown

firedown

 

DI (24 VAC)

J1---10

 

 

 

 

 

Enthalpy Switch

enthalpy

 

DI (24 VAC)

J2---6, 7

 

 

 

 

 

Humidistat Input Status

humstat

 

DI (24 VAC)

J5---7, 8

 

 

 

 

 

 

 

 

 

CONFIGURABLE INPUTS*

 

 

 

 

 

Space Relative Humidity

sprh

 

AI (4---20 ma)

J4---2,3 or J4---5,6

 

 

 

 

 

 

Outside Air Relative Humidity

oarh

 

AI (4---20 ma)

 

 

 

 

 

 

 

Supply Fan Status

fanstat

 

DI (24 VAC)

J5---1,2 or J5---3,4 or

 

 

 

 

 

 

Filter Status

filtstat

 

DI (24 VAC)

 

J5 5,6 or J5---7,8

 

 

 

 

 

 

Remote Occupancy Input

remocc

 

DI (24 VAC)

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUTS

 

 

 

 

 

 

Economizer Commanded Position

econocmd

 

4---20ma

J2---5

 

 

 

 

 

Supply Fan Relay State

sf

 

DO Relay (24VAC , 1A)

J1---4

 

 

 

 

 

Compressor 1 Relay State

comp_1

 

DO Relay (24VAC , 1A)

J1---8

 

 

 

 

 

Compressor 2 Relay State

comp_2

 

DO Relay (24VAC , 1A)

J1---7

 

 

 

 

 

Heat Stage 1 Relay State

heat_1

 

DO Relay (24VAC , 1A)

J1---6

 

 

 

 

 

Heat Stage 2 Relay State

heat_2

 

DO Relay (24VAC , 1A)

J1---5

 

 

 

 

 

Power Exhaust Relay State

aux_2

 

DO Relay (24VAC , 1A)

J11---3

 

 

 

 

 

Dehumidification Relay State

humizer

 

DO Relay (24VAC, 1A)

J11---7, 8

LEGEND

 

 

 

 

AI

---

Analog Input

 

 

 

 

AO ---

Analog Output

 

 

 

 

DI

---

Discrete Input

 

 

 

 

DO ---

Discrete Output

 

 

 

 

*These inputs (if installed) take the place of the default input on the specific channel according to schematic. Parallel pins J5--- 1 = J2--- 6, J5--- 3 = J1--- 10, J5---5 = J1--- 2 are used for field--- installation.

548J*14D

The RTU-MP controller requires the use of a Bryant space sensor. A standard thermostat cannot be used with the RTU-MP system.

Supply Air Temperature (SAT) Sensor —

On FIOP-equipped 548J*14D unit, the unit is supplied with a supply-air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6-inches (12.7 mm) in length. It is a nominal 10-k ohm thermistor.

The SAT is factory-wired. The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2-in. hole in the flange or duct. Use two field-supplied, self-drilling screws to secure the sensor probe in a horizontal orientation. See Fig. 36.

SUPPLY AIR

 

 

ROOF

TEMPERATURE

 

 

SENSOR

SUPPLY AIR

RETURN AIR

CURB

 

 

 

 

 

C10020

Fig. 36 - Typical Mounting Location for Supply Air Temperature (SAT) Sensor on Small Rooftop Units

21

Image 21
Contents Installation Instructions Safety Considerations Unit Dimensional Drawing Size 14 Unit Plan for Unit Location Service Clearance Dimensional DrawingPlan for Sequence of Unit Installation Inspect UnitProvide Unit Support Roof Curb Details For Units with Accessory Electric Heaters Field Fabricate DuctworkRig and Place Unit Install Outside Air Hood Convert to Horizontal and Connect Ductwork when requiredEconomizer Hood Removal and Setup Factory Option Positioning on CurbDamper Assembly Economizer Hood and Two-Position Hood Install External Condensate Trap and LineMake Electrical Connections Field Power SupplyMounting Position for Field Disconnects Over 100A Units with Factory-Installed Disconnect Units Without Factory-Installed DisconnectUnit Powered Convenience Outlet Wiring Factory-Option Thru-Base Connections Field Control WiringThermostat Units without Thru-Base ConnectionsUnit without Thru-Base Connection Kit Heat Anticipator SettingsSingle Point Boxes Heater and Supplementary FusesHeater Low-Voltage Control Connections Outdoor Air Enthalpy Control PNO 33CSENTHSW Return Air Enthalpy SensorDifferential Enthalpy Control RTU-MP Control System RTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Supply Air Temperature SAT SensorSpace Temperature SPT Sensors Outdoor Air Temperature OAT SensorField Connections EconoMi$er2Indoor Air Quality CO2 sensor RTU-MP T-56 Sensor ConnectionsConnecting Discrete Inputs Outdoor Air Quality Sensor PNO 33ZCSENCO2 plusWeatherproof enclosure Local Access Communication Wiring ProtocolsRTU-MP Troubleshooting GeneralLEDs on the RTU-MP show the status of certain functions LEDsSystem Smoke DetectorsController SensorSmoke Detector Locations Supply AirReturn Air with Economizer Return Air Detector Shipping Position Completing Installation of Return Air Smoke SensorNone Unit Wire/Fuse or Hacr Breaker Sizing DataPwrd C.O EconoMi$er IV Occupancy Switch Adjust Factory-Installed OptionsPre-Start and Start-Up Install Accessories548J*14D 548J*14D Catalog No. II548J---07

548J*14D specifications

The Bryant 548J*14D is a highly efficient and versatile air conditioning unit designed to meet the varying demands of residential and light commercial applications. This model stands out due to its advanced engineering, energy-saving features, and reliable performance, making it an ideal choice for homeowners looking to enhance comfort without compromising on energy efficiency.

One of the main features of the Bryant 548J*14D is its excellent SEER (Seasonal Energy Efficiency Ratio) rating, which signifies its ability to provide cooling while consuming less energy. Optimized for efficiency, this unit employs a high-efficiency compressor that adjusts its output based on cooling demands, allowing it to use only the energy necessary to maintain a comfortable environment.

The unit’s all-aluminum evaporator coil ensures durability and resistance to corrosion, contributing to its longer lifespan and consistent performance. Additionally, the Bryant 548J*14D incorporates advanced refrigeration technologies for maximum heat transfer efficiency. This technology not only enhances cooling performance but also improves overall system reliability.

A key characteristic of the Bryant 548J*14D is its Whisper Series technology designed for quiet operation. The low-noise design minimizes sound levels, allowing for unobtrusive cooling in residential spaces while still ensuring effective airflow and cooling capacity. This makes it particularly favorable for installation in bedrooms and other noise-sensitive areas.

Another noteworthy aspect of the Bryant 548J*14D is its compatibility with the MyBryant smartphone app, which enables homeowners to monitor and control their HVAC systems remotely. This connectivity offers convenience and helps to optimize energy usage, as users can adjust settings based on their schedules and preferences.

Furthermore, the Bryant 548J*14D is designed with a robustness that allows it to withstand diverse weather conditions, ensuring reliable performance even in extreme climates. The unit’s compact design eases installation in various settings, whether it's on rooftops, near walls, or on concrete pads.

In summary, the Bryant 548J*14D is a cutting-edge air conditioning unit that combines energy efficiency, quiet operation, and advanced technologies. With its robust construction, smart features, and reliable performance, it stands as a valuable solution for anyone looking to enhance comfort and save on energy costs in their homes or light commercial environments.