Bryant 548J*14D RTU-MP T-56 Sensor Connections, Indoor Air Quality CO2 sensor

Page 23

SEN J20-1

SEN J20-2

Jumper

SET

SET J20-3

C08461

Fig. 40 - RTU-MP T-56 Sensor Connections

Connect T-59:The T-59 space sensor requires a separate, isolated power supply of 24 VAC. See Fig. 41 for internal connections at the T-59. Connect the SEN terminal (BLU) to RTU-MP J20-1. Connect the COM terminal (BRN) to J20-2. Connect the SET terminal (STO or BLK) to J20-3.

Indoor Air Quality (CO2 sensor) —

The indoor air quality sensor accessory monitors space carbon dioxide (CO2) levels. This information is used to monitor IAQ levels. Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infrared technology to measure the levels of CO2 present in the space air.

The CO2 sensors are all factory set for a range of 0 to 2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO2 sensor for electrical requirements and terminal locations. See Fig. 42 for typical CO2 sensor wiring schematic.

548J*14D

BLK (STO)

BRN (COM)

BLU (SPT)

OR SET SEN

OPB COM- PWR+

24 VAC

J20-3

J20-2SENSOR WIRING

J20-1

POWER

WIRING

H G 24 VAC OR

+ - 24 VDC

+ 0-10VDC

- SIG COM + 4-20mA

NC }ALARM

COM RELAY

NO CONTACTS

2 1 8 7 6 5 4 3 2 1

J3 J4

C08635

NOTE: Must use a separate isolated transformer.

C10291

Fig. 41 - Space Temperature Sensor Typical Wiring

(33ZCT59SPT)

Economizer Controls —

To wire the return air enthalpy sensor, perform the following:

1.Use a 2-conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthal- py controller.

2.Connect the field-supplied RED wire to (+) spade connector on the return air enthalpy sensor and the

(+)terminal on the enthalpy controller. Connect the BLK wire to (-) spade connector on the return air en- thalpy sensor and the (-) terminal on the enthalpy controller.

Fig. 42 - Indoor/Outdoor Air Quality (CO2) Sensor

(33ZCSENCO2) - Typical Wiring Diagram

To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return-air grille (if present) so it senses the concentration of CO2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact.

Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.

Wiring the Indoor Air Quality Sensor: For each sensor, use two 2-conductor 18 AWG (American Wire Gage) twisted-pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.

23

Image 23
Contents Installation Instructions Safety Considerations Unit Dimensional Drawing Size 14 Unit Plan for Unit Location Service Clearance Dimensional DrawingProvide Unit Support Plan for Sequence of Unit InstallationInspect Unit Roof Curb Details Rig and Place Unit For Units with Accessory Electric HeatersField Fabricate Ductwork Positioning on Curb Convert to Horizontal and Connect Ductwork when requiredInstall Outside Air Hood Economizer Hood Removal and Setup Factory OptionDamper Assembly Economizer Hood and Two-Position Hood Install External Condensate Trap and LineMake Electrical Connections Field Power SupplyMounting Position for Field Disconnects Over 100A Units with Factory-Installed Disconnect Units Without Factory-Installed DisconnectUnit Powered Convenience Outlet Wiring Units without Thru-Base Connections Field Control WiringFactory-Option Thru-Base Connections ThermostatUnit without Thru-Base Connection Kit Heat Anticipator SettingsHeater Low-Voltage Control Connections Single Point BoxesHeater and Supplementary Fuses Differential Enthalpy Control Outdoor Air Enthalpy Control PNO 33CSENTHSWReturn Air Enthalpy Sensor RTU-MP Control System RTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Supply Air Temperature SAT SensorEconoMi$er2 Outdoor Air Temperature OAT SensorSpace Temperature SPT Sensors Field ConnectionsIndoor Air Quality CO2 sensor RTU-MP T-56 Sensor ConnectionsWeatherproof enclosure Connecting Discrete InputsOutdoor Air Quality Sensor PNO 33ZCSENCO2 plus General Communication Wiring ProtocolsLocal Access RTU-MP TroubleshootingLEDs on the RTU-MP show the status of certain functions LEDsSensor Smoke DetectorsSystem ControllerReturn Air with Economizer Smoke Detector LocationsSupply Air Return Air Detector Shipping Position Completing Installation of Return Air Smoke SensorNone Unit Wire/Fuse or Hacr Breaker Sizing DataPwrd C.O EconoMi$er IV Occupancy Switch Adjust Factory-Installed OptionsPre-Start and Start-Up Install Accessories548J*14D 548J*14D Catalog No. II548J---07

548J*14D specifications

The Bryant 548J*14D is a highly efficient and versatile air conditioning unit designed to meet the varying demands of residential and light commercial applications. This model stands out due to its advanced engineering, energy-saving features, and reliable performance, making it an ideal choice for homeowners looking to enhance comfort without compromising on energy efficiency.

One of the main features of the Bryant 548J*14D is its excellent SEER (Seasonal Energy Efficiency Ratio) rating, which signifies its ability to provide cooling while consuming less energy. Optimized for efficiency, this unit employs a high-efficiency compressor that adjusts its output based on cooling demands, allowing it to use only the energy necessary to maintain a comfortable environment.

The unit’s all-aluminum evaporator coil ensures durability and resistance to corrosion, contributing to its longer lifespan and consistent performance. Additionally, the Bryant 548J*14D incorporates advanced refrigeration technologies for maximum heat transfer efficiency. This technology not only enhances cooling performance but also improves overall system reliability.

A key characteristic of the Bryant 548J*14D is its Whisper Series technology designed for quiet operation. The low-noise design minimizes sound levels, allowing for unobtrusive cooling in residential spaces while still ensuring effective airflow and cooling capacity. This makes it particularly favorable for installation in bedrooms and other noise-sensitive areas.

Another noteworthy aspect of the Bryant 548J*14D is its compatibility with the MyBryant smartphone app, which enables homeowners to monitor and control their HVAC systems remotely. This connectivity offers convenience and helps to optimize energy usage, as users can adjust settings based on their schedules and preferences.

Furthermore, the Bryant 548J*14D is designed with a robustness that allows it to withstand diverse weather conditions, ensuring reliable performance even in extreme climates. The unit’s compact design eases installation in various settings, whether it's on rooftops, near walls, or on concrete pads.

In summary, the Bryant 548J*14D is a cutting-edge air conditioning unit that combines energy efficiency, quiet operation, and advanced technologies. With its robust construction, smart features, and reliable performance, it stands as a valuable solution for anyone looking to enhance comfort and save on energy costs in their homes or light commercial environments.