ENVISION SERIES AIR HANDLER INSTALLATION MANUAL

General Installation Information

Condensate Drain

To facilitate condensate removal, the air handler should be pitched 1/4” towards the drain in both directions. The drain line contains cold water and should be insulated in uncondi- tioned spaces to avoid drain line condensation from drip- ping on ceiling, etc. The drain pan has a primary and aux- iliary drain connection. The air handler drain connections must be connected to a drain line and pitched away from the unit a minimum of 1/8” per foot to allow the condensate to flow away from the air handler. A trap must be installed in the drain line below the bottom of the drain pan to en- sure free condensate flow (units are not internally trapped). The primary condensate drain must be terminated to an

!">D1 1]c^ZW\U

!

#

DS\bWT\SSRSR

!">D1

&^S`T]]b

open drain or sump. Do not connect the condensate drain to a closed waste system. An open vertical air vent should be installed to overcome line length, friction and static pres- sure. It is recommended that the auxiliary drain be connect- ed to a drain line for all units. The auxiliary drain should be run to an area where the homeowner will notice it draining. The drain line should not be smaller than the drain connec- tion at the condensate pan. If the air handler is located in an unconditioned space, water in the trap may freeze. It is recommended that the trap material be of a type that will allow for expansion of water when it freezes. Drain lines must be in conformance with local codes.

Air Handler Configuration

The Envision Air Handler is factory configured for upflow and horizontal left hand air discharge installation (Figure 1). For bottomflow or horizontal right hand discharge, certain field modifications are required.

Warning: Do not lift or reposition the ‘A’ coil by grasping the copper tube header or distributor. This could cause a tubing fracture resulting in a refrigerant leak.

Figure 1 - Factory configuration is top discharge and horizontal left hand air discharge.

5

Image 6
Contents Envision Series Air Handler Installation Manual WaterFurnace Table of Contents Nomenclature Initial InspectionGeneral Installation Information Safety ConsiderationsMoving and Storage Unit LocationDuct System Air Handler Configuration Condensate DrainBottomflow Application Connection to the Coil Air Handler InstallationLeak Testing System EvacuationCharging the System TXV Superheat AdjustmentsRefrigeration Refrigerant Line SizingDecrease Superheat Open Valve Increase Superheat Close Valve Hydronic Models =/2CCoil Capacity vs. Entering Water Temperature Electrical DataWater Presure Drop Hydronic Coil Low Voltage Point to Point Wiring 208v 240vWiring Schematic 208-230/60/1`6O\RZS`e YE3ZSQb`WQ6SOb Cooling/Heating settings Dehumidification Mode settingsECM Blower Control Dip Switch Settings Blower PerformanceBlower Motors Maintenance FiltersUnit Start Up Air CoilDimensional Data Top Flow/Horizontal Unit ConfigurationBottom Flow Unit Configuration =D73E @=BD73E @756BA723D73E =BB=D73EReplacement Procedures Warranty Material ReturnObtaining Parts Product

IM1603 specifications

Envision Peripherals IM1603 is a state-of-the-art display solution designed to cater to the diverse needs of various sectors, including retail, corporate, and education. This innovative device combines advanced technology with user-friendly features, making it a robust choice for organizations looking to enhance their visual communication strategies.

One of the standout features of the IM1603 is its high-definition display, which boasts impressive resolution and vivid color accuracy. With its 16:9 aspect ratio, the screen offers a cinematic viewing experience, making it perfect for sharing presentations, videos, and graphics in high clarity. The touchscreen functionality adds to its versatility, allowing users to interact directly with the display. This is particularly beneficial in educational environments where interactive learning tools are essential.

The IM1603 is built with durability in mind. It features a rugged design that can withstand the rigors of daily use, ensuring that it remains functional in busy settings. This reliability is complemented by the enhanced brightness levels, which ensure that the content is easily viewable even in well-lit environments. The anti-glare surface minimizes reflections, making it user-friendly for both presenters and viewers.

Connectivity is another strong point of the Envision Peripherals IM1603. It comes equipped with multiple input options, including HDMI, VGA, and USB ports, enabling seamless integration with various devices such as laptops, media players, and cameras. This flexibility ensures that users can easily switch between different sources without the need for complicated setups.

Moreover, the IM1603 incorporates advanced LED technology, which not only improves energy efficiency but also extends the lifespan of the display. This means that organizations can enjoy long-term use without the frequent need for replacements, making it a cost-effective solution.

In terms of installation, the IM1603 offers several mounting options, including wall mounts and stands, providing flexibility to fit different setups. This adaptability makes it suitable for a wide range of applications, from digital signage in retail spaces to interactive presentations in corporate environments.

In conclusion, the Envision Peripherals IM1603 stands out as a premier display solution that combines exceptional visual quality, durability, and connectivity. Its advanced features cater to the needs of various industries, making it an ideal choice for those seeking to elevate their display capabilities. With the IM1603, organizations can engage their audiences more effectively and create impactful visual experiences.