ENVISION SERIES AIR HANDLER INSTALLATION MANUAL

General Installation Information

Bottomflow Application

To convert the NAH series air handlers for bottomflow ap- plications follow the steps shown below:

1.Remove all access panels. Disconnect the blower harnesses from the motor and loosen ground wire from blower. Remove the blower by removing 2 screws from the blower mounting bracket, and slide the blower assembly out the front. Remove the stiffener bracket in front of coil, 'A' coil/pan assembly and the horizontal drain pan. This will lighten the cabinet and make it easier to maneuver.

2.Rotate the cabinet 180° from the upright position so that the discharge air opening is located at the bottom and the return air opening is at the top.

3.Install the blower assembly into the blower discharge opening at the bottom of the cabinet by sliding the blower mounting bracket under the discharge support bracket and secure in place with 2 screws. The blower harness and motor ground wire should be reattached before sliding the blower into place.

4.On the NAH042-060 install the NAHBC bottomflow conversion kit per instructions in the kit. Failure to install this kit will result in condensate blow-off from the 'A' coil into the cabinet and ductwork.

5.Install the 'A' coil into the upper section of the cabinet as pictured in Figure 2. Attach the stiffener bracket into the two holes provided in the cabinet so that the bracket is in front of the coil. The horizontal drain pan is not needed and must be discarded. Plug the 2 drain hole openings in the access panel with the plugs provided.

6.Replace the access panels.

7.Bottom air discharge units require the supply air opening to be cut at least a 1/2” larger than the unit’s air outlet.

8.When installed on combustible flooring, protect the edges of the floor opening with sheet metal over wrap or

other non-combustible material.

9.Bottom air discharge units should be sealed well to the floor to prevent air leakage.

Figure 2 - Bottomflow NAH.

Horizontal Right Air Discharge

Application

To convert the NAH series air handlers for horizontal right air discharge applications follow the steps shown below

1.Remove all access panels. Remove the stiffener bracket in front of the coil, ‘A’ coil assembly and the horizontal drain pan.

2.From the vertical upflow position, rotate the top of the cabinet 90° to the right and set in place.

3.Remove the support bracket mounted to the top plate of the ‘A’ coil. Rotate the ‘A’ coil support bracket 180° from its original position and re-attach into existing holes in the top plate of the coil. This must be done to prevent the ‘A’ coil from falling into the drain pan (Figure 3).

4.Move the horizontal drain pan from the left side of the ‘A’ coil to the right hand side of the ‘A’ coil. Place the ‘A’ coil and horizontal drain pan assembly into the cabinet

so that the support bracket is resting in the horizontal drain pan as shown in Figure 3. Attach the stiffener bracket into the two holes provided in the cabinet so that the bracket is in front of the coil.

5.Remove the 2 drain plugs from the upper right of the access panel and install them on the lower left of the access panel. Replace the access panels.

6.If the unit is suspended, the entire length of the cabinet should be supported.

Figure 3 - Horizontal Right Hand Air Discharge

Rotate the coil support bracket to this position

Important: When removing the coil, there is possible dan- ger of equipment damage and personal injury. Be careful when removing the coil assembly from the unit.

6

Image 7
Contents Envision Series Air Handler Installation Manual WaterFurnace Table of Contents Initial Inspection NomenclatureSafety Considerations General Installation InformationUnit Location Moving and StorageDuct System Condensate Drain Air Handler ConfigurationBottomflow Application System Evacuation Air Handler InstallationLeak Testing Connection to the CoilRefrigerant Line Sizing TXV Superheat AdjustmentsRefrigeration Charging the SystemDecrease Superheat Open Valve Increase Superheat Close Valve =/2C Hydronic ModelsElectrical Data Coil Capacity vs. Entering Water TemperatureWater Presure Drop Hydronic Coil 208v 240v Low Voltage Point to Point Wiring208-230/60/1 Wiring Schematic`6O\RZS`e YE3ZSQb`WQ6SOb Dehumidification Mode settings Cooling/Heating settingsECM Blower Control Blower Performance Dip Switch SettingsAir Coil Maintenance FiltersUnit Start Up Blower MotorsTop Flow/Horizontal Unit Configuration Dimensional Data=D73E @=BD73E @756BA723D73E =BB=D73E Bottom Flow Unit ConfigurationWarranty Material Return Replacement ProceduresObtaining Parts Product

IM1603 specifications

Envision Peripherals IM1603 is a state-of-the-art display solution designed to cater to the diverse needs of various sectors, including retail, corporate, and education. This innovative device combines advanced technology with user-friendly features, making it a robust choice for organizations looking to enhance their visual communication strategies.

One of the standout features of the IM1603 is its high-definition display, which boasts impressive resolution and vivid color accuracy. With its 16:9 aspect ratio, the screen offers a cinematic viewing experience, making it perfect for sharing presentations, videos, and graphics in high clarity. The touchscreen functionality adds to its versatility, allowing users to interact directly with the display. This is particularly beneficial in educational environments where interactive learning tools are essential.

The IM1603 is built with durability in mind. It features a rugged design that can withstand the rigors of daily use, ensuring that it remains functional in busy settings. This reliability is complemented by the enhanced brightness levels, which ensure that the content is easily viewable even in well-lit environments. The anti-glare surface minimizes reflections, making it user-friendly for both presenters and viewers.

Connectivity is another strong point of the Envision Peripherals IM1603. It comes equipped with multiple input options, including HDMI, VGA, and USB ports, enabling seamless integration with various devices such as laptops, media players, and cameras. This flexibility ensures that users can easily switch between different sources without the need for complicated setups.

Moreover, the IM1603 incorporates advanced LED technology, which not only improves energy efficiency but also extends the lifespan of the display. This means that organizations can enjoy long-term use without the frequent need for replacements, making it a cost-effective solution.

In terms of installation, the IM1603 offers several mounting options, including wall mounts and stands, providing flexibility to fit different setups. This adaptability makes it suitable for a wide range of applications, from digital signage in retail spaces to interactive presentations in corporate environments.

In conclusion, the Envision Peripherals IM1603 stands out as a premier display solution that combines exceptional visual quality, durability, and connectivity. Its advanced features cater to the needs of various industries, making it an ideal choice for those seeking to elevate their display capabilities. With the IM1603, organizations can engage their audiences more effectively and create impactful visual experiences.