3-12. Electrical Service Guide
Input Voltage | 230 | 460 | 575 | |
|
|
|
| |
Input Amperes At Rated Output | 69 | 34.5 | 27.5 | |
|
|
|
| |
Max Recommended Standard Fuse Rating In Amperes 1 |
|
|
| |
80 | 40 | 30 | ||
Normal Operating 3 | 100 | 50 | 40 | |
|
|
|
| |
Min Input Conductor Size In AWG 4 | 4 | 8 | 10 | |
|
|
|
| |
Max Recommended Input Conductor Length In Feet (Meters) | 237 | 422 | 444 | |
(72) | (129) | (135) | ||
| ||||
|
|
|
| |
Min Grounding Conductor Size In AWG 4 | 8 | 10 | 10 | |
|
|
|
|
Reference: 2005 National Electrical Code (NEC)
1Consult factory for circuit breaker applications.
2
3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).
4Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table 310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
3-13. Placing Jumper Links
Y Disconnect and lockout/tag- out input power before installing or moving jumper links.
Check input voltage available at site.
1 Jumper Link Label
Check label − only one is on unit.
2 Jumper Links
Move jumper links to match input voltage.
Close and secure access door, or go on to Section
1
230 VOLTS | 460 VOLTS | 575 VOLTS |
|
| Ref. |
2
Tools Needed: |
|
3/8 in |
|
3/8 in | Do not overtighten |
| jumper link nuts. |
| Ref. 800 |