SECTION 7 − OPERATING AUXILIARY EQUIPMENT
7-1. 120 Volt Duplex And Optional GFCI Receptacles
|
|
|
|
|
| 1 | 2 |
|
| ||||||
|
|
|
|
|
|
|
|
4
3
YIf unit does not have GFCI re- ceptacles, use
1120 V 15 A AC Receptacle RC1
2120 V 15 A AC Receptacle RC2
3120 V 20 A AC GFCI Receptacles GFCI1 And GFCI2 (Optional)
Receptacles supply 60 Hz single- phase power at weld/power speed.
4Circuit Breakers CB1 And CB2
CB1 protects RC1/GFCI1 and CB2 protects RC2/GFCI2 from over- load. If CB1 or CB2 opens, the receptacle does not work.
.If a circuit breaker continues to open, contact Factory Autho- rized Service Agent.
If a ground fault is detected, GFCI Reset button pops out and receptacle does not work. Check for faulty tools plugged in receptacle. Press button to reset.
.At least once a month, run en-
gine at weld/power speed and press test button to verify GFCI is working properly.
Maximum output from each duplex receptacle is 1.8 kVA/kW, and 3 kVA/kW from all receptacles. Gen- erator power is not affected by weld output.
EXAMPLE: If 15 A is drawn from RC1, only 10 A is available at RC2:
(120 V x 15 A) + (120 V x 10 A) = 3.0 kVA/kW
Ref. 206 029