Sanyo SAP-KRV123EH, SAP-KRV93EH, SAP-CRV93EH Overload prevention during heating, Freeze prevention

Page 36

9-2. Protective Functions

Overload prevention during heating

During HEAT operation, the temperature of the indoor heat exchanger is used to control the frequency and lessen the load on the compressor before the protective device is activated.

Indoor heat exchanger temperature (°C)

Approx.

 

A

Indoor heat exchanger

 

A. Control start

53

 

 

 

 

B. Control end

 

 

 

Approx.

 

 

 

B

47

 

 

 

 

 

a

b

c

d

aArea: Automatic capacity control

bWhen Point A has been exceeded, the operation frequency is reduced by a certain proportion.

cArea: Frequency increase is prohibited.

dAt Point B and below, overload prevention is ended and control is the same as in the a area.

Freeze prevention

During COOL or DRY operation, freezing is detected and operation is stopped when the temperature of the indoor heat exchanger matches the conditions below.

1Freeze-prevention operation is engaged when the temperature of the indoor heat exchanger is below 6°C.

2Restart after freeze-prevention operation occurs when the temperature of the indoor heat exchanger reaches 8°C or above.

Indoor heat exchanger temperature (°C)

8

 

 

C

 

 

 

6

A

B

 

 

 

 

2

 

 

 

*

 

 

 

 

a

b

c

d

aArea: Automatic capacity control

bWhen the temperature drops below Point A, the operation frequency is reduced by a certain proportion.

cArea: Frequency increase is prohibited.

dWhen the temperature reaches Point C or above, freezing prevention is ended and control is the same as in the a area.

*When the temperature drops to below 2°C (continuously for 2 minutes or longer), the compressor stops.

Once the freeze condition is detected, the air conditioner will work less than the maximum frequency until it is turned off.

Cold-air prevention during heating

During heating, the fan speed is set to “LL” (very low) or stopped. As the temperature of the indoor heat exchanger rises, the fan speed is changed to the set speed.

High

 

 

Set fan speed

 

 

 

 

Normal operation

 

 

 

 

At start of operation

LL

 

 

 

Stopped

25

30

Approx. 40

 

Indoor heat exchanger

temperature (°C)

NOTE

The fan speed is forcibly changed to “LL” beginning 30 seconds after the thermostat turns OFF.

Normal operation refers to operation when the room temperature has approached the set temperature.

When HEAT operation starts, the indoor fan is stopped until the temperature of the indoor heat exchanger reaches 20°C or higher, or until the room temperature reaches 15°C or higher.

Compressor discharge temperature control

This function controls the operation frequency to prevent the compressor discharge temperature from rising more than a specified temperature.

Compressor discharge temperature (°C)

Approx.

A

 

 

101

 

 

 

Approx.

 

 

B

94

 

 

 

a

b

c

d

aArea: Automatic capacity control.

bWhen the temperature rises above Point A, the operation frequency is reduced at a specified rate.

cArea: Further frequency increase is prohibited.

dWhen the temperature falls below Point B, prevention of a rise in frequency is released and the air conditioner operates as in a area.

*The compressor will stop if the temperature of the compressor discharge exceeds 120°C due to shortage of gas or other reason.

36

Image 36
Contents DC Inverter Split System AIR Conditioner Please Read Before Starting Table of Contents Temperature Indoor Air Intake Temp Outdoor Air Intake Temp Operating RangeSpecifications Unit SpecificationsIndoor Unit SAP-KRV93EHSAP-KRV123EH Outdoor Unit SAP-CRV123EHMajor Component Specifications SAP- KRV93EHSAP- KRV123EH Outdoor Unit Outdoor Unit SAP- CRV93EHOutdoor Unit SAP- CRV123EH Other Component Specifications Indoor Unit SAP- KRV93EHSAP- CRV123EH Data Ø65SAP-CRV123EH AIR DischargeRefrigerant Flow Diagram Refrigerant Flow DiagramInsulation of Refrigerant Tubing Proper insulation material. The thickness of the insulationTemperature Charts Performance DataIndoor Unit SAP-KRV93EH Outdoor Unit SAP-CRV93EH Indoor Unit SAP-KRV123EH Outdoor Unit SAP-CRV123EH Indoor Air TempAir Throw Distance Charts Axis air Vertical Operating Frequency Charts 230V Single-phase 50HzIndoor Unit SAP- KRV93EH Outdoor Unit SAP- CRV93EH CoolingHeating Indoor Unit SAP- KRV123EH Heating Electrical Data Electric Wiring Diagrams Outdoor Unit Indoor UnitSAP-CRV93EH SAP-KRV93EH SAP-CRV123EH SAP-KRV123EH Indoor Unit SAP-KRV123EHInstallation Instructions Installation Site SelectionAvoid Out Recommended Wire Length and Diameter Wiring System DiagramRemote Control Unit Installation Position To take out the remote control unit, pull it forwardHow to Test Run the Air Conditioner Remove the Grille to Install the Indoor Unit Maintenance Address Setting of the Remote Control UnitHow to Disconnect Emergency operation Auto cooling/heating operationPAM-αcontrol Timer backup Lamp colorsCompressor discharge temperature control Overload prevention during heatingFreeze prevention Cold-air prevention during heatingDefrost detection and release CT Peak current cut-off controlPrecautions before performing inspection or repair Method of self-diagnosticsExecuting self-diagnostics S01 S02S03 S04If self-diagnostics function fails to operate Checking the outdoor unitChecking serial communications NormalDiagnostic procedure Diagnostic resultsRemedy for symptom 3 to Measurement location Normal valueNoise malfunction and electromagnetic interference Noise malfunctionElectromagnetic interference Checking Electrical Components Measurement of Insulation ResistanceChecking Continuity of Fuse on PCB Ass’y Refrigerant R410A Special Precautions When Servicing Unit Characteristics of New Refrigerant R410AChecklist Before Servicing HFC32 50% / HFC125 50%Tubing precautions No addition of compressor oil for R410ANo use of refrigerant other than R410A If refrigerant R410A is exposed to fireTubing Installation Procedures Tools Specifically for R410ACase of Compressor Malfunction Configuration and characteristics of cylinders RechargingUnit. This may cause dam- age to the compressor ExampleCase Refrigerant is Leaking Welding leaking pointsCharging Additional Refrigerant Retro-Fitting Existing SystemsOI-852-6-4180-671-00-0 Features Contents Alert SymbolsProduct Information Installation Location Safety InstructionsElectrical Requirements Names of Parts Indoor UnitOutdoor Unit Unit Display and Operation Button Remote Control Unit Display Remote Control Unit Hour OFF TimerOn Time Auto HeatDRY CoolUsing the Remote Control Unit Temperature Display SelectorHow to Install Batteries Button Time Display Selector buttonUsing the Remote Control Unit Rear side Remote control unit mountMounting screws 4 x 16 included HoleOperation with the Remote Control Unit StepPress the ON/OFF operation button Operation with the Remote Control Unit Manual OperationAdjusting the Fan Speed Night Setback Mode is used for saving energy Cooling and DRY ModeSetting TemperatureQuiet Mode Special Remarks Setting the Timer Operation IndicationSetting the Timer To cancel a timer program Press the Cancel button1030 pm 710 am 1100 am Present time OFFUsing the 1-Hour OFF Timer Setting procedureCancellation procedure Operation together with the Daily ON/OFF Repeat TimerAdjusting the Airflow Direction Cool Sweep DRY FAN HeatOperation without the Remote Control Unit Care and CleaningWhen the air conditioner is not running Care and Cleaning Air intake grille Anti-mold filter CleaningSuffocation in extreme cases FilterTroubleshooting Operating RangeTrouble Possible Cause Remedy Osaka, Japan SM700590 FEB/2004
Related manuals
Manual 25 pages 39.04 Kb

SAP-CRV93EH, SAP-CRV123EH, SAP-KRV93EH, SAP-KRV123EH specifications

The Sanyo SAP-KRV93EH and SAP-KRV123EH are innovative air conditioning units that stand out in the market for their performance, energy efficiency, and user-friendly features. Designed to cater to various cooling needs, these models are suitable for both residential and commercial spaces, ensuring comfort in every environment.

One of the main features of both models is their advanced inverter technology. This technology allows the air conditioners to adjust the compressor speed according to the desired temperature, offering precise climate control while significantly reducing energy consumption. This not only translates to lower electricity bills but also minimizes the environmental impact, making the SAP-KRV93EH and SAP-KRV123EH eco-friendly options.

The SAP-KRV93EH has a cooling capacity of 9,000 BTU, while the SAP-KRV123EH boasts an impressive 12,000 BTU. This range ensures that users can choose the appropriate unit according to the size of the room or area requiring cooling. The units are equipped with high-efficiency filters that purify the air, removing dust, allergens, and other particulates. This feature is particularly beneficial for those with allergies or respiratory issues, providing a healthier indoor environment.

In terms of user interface, both models are designed with ease of use in mind. They include a remote control that allows users to adjust settings without needing to get up. Additionally, the units have a programmable timer, ensuring that users can set the air conditioning to operate only when needed, enhancing convenience and energy savings.

Another notable technology present in these models is the “Smart Duct” airflow system. This system optimizes air distribution, allowing for an even distribution of cooled air throughout the room. This means fewer hot spots, leading to a more comfortable living or working space.

Both the SAP-KRV93EH and SAP-KRV123EH have sleek designs that blend well with various interior styles, allowing them to fit seamlessly into homes or offices. Furthermore, they operate quietly, ensuring that users can enjoy a peaceful environment.

Overall, the Sanyo SAP-KRV93EH and SAP-KRV123EH air conditioning units combine advanced technology, energy efficiency, and practical features, making them an excellent choice for those looking to enhance their comfort while being conscious of energy usage. With their robust performance and user-friendly attributes, these models epitomize what modern air conditioning solutions should offer.