Schumacher PST-1000 owner manual Voltage Amps Likely Cause, INSULATED-POS Circuit Test

Page 6

VOLTAGE

AMPS

LIKELY CAUSE

Below 9.6

High

Bad starter or a very hot or

 

 

cold engine

Below 9.6

Low

Bad Battery or Loose Battery

 

 

Terminals

Above 9.6

Low

Bad Connections at Starter or

 

 

Solenoid

INSULATED-POS CIRCUIT TEST

1.Set the Volts Selector to “External” (±199.9V. scale)

2.Connect Volt test leads as shows in the following (Figure 3). Clip from battery POS (+) post to the input terminal on the starter motor.

BLACK

STARTER

-POS +

BATTERY

CHASSIS

SOLENOID RELAY

Figure 3

Connections For INSULATED-POS CIRCUIT TEST

1.Disable ignition (as described earlier) to prevent engine from starting during test.

2.Operate starter and read voltmeter while cranking.

3.Test Conclusion: Good circuits drop less than 0.4 volt on a 6 volt system and less than 0.5 volt on 12 volt systems. If okay, go to the Ground Circuit Test. If an excessive voltage drop is detected, further isolate the problem by retesting across the individual circuit components.

12 VOLT CRANKING CIRCUIT

TYPICAL VOLTAGE DROP MAXIMUMS

Each Cable

0.2

volt

Each connection

0.1

volt

Solenoid Switch

0.3

volt

GROUND-NEG CIRCUIT TEST

Trouble can be caused by a poor ground connection, a loosed starter motor mounting bolt, a bad battery terminal post connec- tor, or a damaged cable from battery to engine block.

1.Select External Volts (±199.9V display)

2.Connect Volt test leads to battery NEG (-) post and starter motor case. Scratch through paint with clip if necessary for good connection.

 

RED

BLACK

STARTER

- NEG

+

BATTERY

 

CHASSIS

Figure 4

Connection For GROUND-NEG CIRCUIT TEST

3.With ignition disabled, crank engine and watch voltmeter to see that reading is not too high.

4.Test Conclusion: A good circuit will typically have less than 0.2 volt drop. If okay, go to Solenoid Control Switch Test, but if not, isolate the cause of excess voltage drop by testing across each circuit part.

SOLENOID CONTROL SWITCH TEST

1.Selection External ±199.9V display

2.Connect Volts test leads to both solenoid switch terminals. Battery voltage should be seen at this time

3.Disable the ignition so the vehicle will not start.

4.Turn the key switch to crank the engine while reading the voltage

5.Test Conclusion : Less than 0.5 volt drop indicates good connections. If the voltage drop is higher, measure the voltage across the switches and wires along the circuit to further isolate.

KEY SWITCH

TRANSMISSION

SAFETY

SWITCH

STARTER

BATTERY

CHASSIS

SOLENOID RELAY

 

Figure 5

Connection For SOLENOID CONTROL SWITCH TEST

6

Image 6
Contents Electric Corporation MT. PROSPECT, IL Must be Dealt with Very Carefully Outstanding Features of the Charging System Analyzer areAnalyzer Features Battery Cables Contact Physician ImmediatelyBattery Testing Timer Beeper and Time OUT LampBattery Caution Amps DisplayLoad Test Electrolyte CautionState of Charge Check Electrolyte Temp Minimum Loaded Volts Load Test CautionDiagnostic Test Procedure Typical Starter Cranking DrawEngine Size INSULATED-POS Circuit Test Solenoid Control Switch TestVoltage Amps Likely Cause Volt Cranking Circuit Typical Voltage Drop MaximumsBattery Goes Above If Battery has LOW ChargeRUN Engine with Accessories OFF Alternator System TestsLoad Requirement Test Regulator Ground TestExternal Regulator Caution Full Fielding Amperage TestTest Procedures Series Parallel SwitchBattery Load Test Steps for External Regulator Type ALTERNA- TORTest Procedure Test ConclusionsAlternator Output Current Test Transformer Rectifier Analyzer Care TroubleshootingSeries Parallel Circuit Unusual Analyzer OperationLimited Warranty