(2)If the
Is the fuse blown?
Normal
Replace the controller.
•No indicators illuminate and the indoor fan does not rotate.
•Check the power voltage.
Blown
Replace the circuit board or the fuse.
9-3. Checking the Indoor and Outdoor Units
(1) Checking the indoor unit
No. | Control | Check items (unit operation) |
1 | Use the remote controller to operate the | • The rated voltage must be present between |
| unit in "TEST run" mode. To determine | • Connect a 5 k ohm resistor between |
| whether the mode is currently in | voltage at both ends is measured, approximately 12 to 15V DC must |
| "TEST run" mode, check the 4 indicator | be output and the multimeter pointer must bounce once every 8 |
| lamps on the unit. If all 4 are blinking, | seconds. |
| the current mode is "TEST run." | Or instead of measuring the voltage, you can insert an LED jig and |
|
| check that the LED flickers once every 8 seconds. |
If there are no problems with the above, then check the outdoor unit. | ||
For the "Test run" procedure, refer to the Appendix B "Installation Instructions". | ||
(2) Checking the outdoor unit |
| |
|
|
|
No. | Control | Check items (unit operation) |
1 Apply the rated voltage between outdoor | • The control panel LED (red) must illuminate. | |
| unit terminals L and N. |
|
2
If there are no problems with the above, then check the indoor unit.
Using the |
| |||||||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
TEST/MV : Compresses time to 1/60th (accelerates |
|
|
|
|
|
|
|
|
|
|
operation by 60 times faster than normal). |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| (TEST)/MV |
|
| COM |
39