Panasonic E8RS, FP0T32CP, FP0-C16T, E32RS Interfaces, Input specifications, Output specifications

Page 18

FP0 Series

Specifica tion Tables

Interfaces

Item

Description

 

Programming TOOL port

RS232, mini DIN socket (5 pin), 9600 or 19200 BAUD, (8 data bits, odd parity, 1 stop bit), Computer link for pro-

 

gramming and communication with MEWTOCOL-COM, user configurable modem connection

 

 

RS232 (SD, RD, GND) 3 way screw terminal, 300 to 19200 BAUD, (7 or 8 data bits, none/even/odd parity,

 

Communication COM port

1 or 2 stop bits, start code: none/STX, end code: CR/CR+LF/ETX/none, CCU mode for programming and com-

 

munication with MEWTOCOL.COM, user configurable modem connection, GENERAL PURPOSE MODE control-

 

 

led by programme for general purpose RS232 communication

 

Input specifications

Item

Description

 

Insulation method

Optical coupler

 

Rated input voltage

24VDC

 

Operating voltage range

21.6 to 26.4VDC

 

Rated input current

4.3mA or less (at 24VDC)

 

Input points per common

6 points/common (C10RS) 8 points/common (C14RS,C16T/C16P,E16T/E16P) 16 points/common (C32T/C32P,E32T/E32P)

 

ON voltage/ON current

19.2V or less/ 3mA or less

 

OFF voltage/OFF current

2.4V or more/ 1mA or more

 

Input impedance

Approx. 5.6kΩ

 

 

50µs or less (at X0,X1) *

 

 

OFFON

100µs or less (at X2 to X5)

 

Response time

 

2ms or less (at X6 to XF)

 

 

ONOFF

Same as above

 

Operating indicator

 

LED display

 

*: Since the response time of X0 to X5 is very fast (for high-speed counter input), the FP0 happens to catch chattering noise as an input signal. To prevent this, it is recommended that timer instruction should be included in the programme.

Output specifications

1) Relay output type

Item

Description

Output type

Normally open (1 Form A)

Rated control capacity

2A 250VAC, 2A 30VDC (4.5A/common)

Response time

OFFON

10ms or less

ONOFF

8ms or less

 

Life

Mechanical

20million operations or more

Electrical

100k operations or more

 

Surge absorber

None

Operation indicator

LED display

The FP0 series conforms to the following standards under the EMC Directive and the Low Voltage Directive.

EMC Directive (89/336/EEC)

Low Voltage Directive (73/23/EEC)

EN 50081-2: 1993

VDE 0160: 1988 (EN 50178: 1995)

EN 50082-2: 1995

(Overvoltage Category II,

 

non-mains-circuit, pollution degree 2)

 

EN 61131-2: 1995

2) Transistor output type

Item

 

 

Description

Insulation method

 

 

Optical coupler

Output type

 

 

Open collector

Rated load voltage

 

 

24VDC 5 to 24VDC

Load voltage allowable range

4.75 to 26.4VDC

Max. load current

 

 

0.1A/points (at DC26.4V) (1A/common) 1

Max. inrush current

 

 

0.3A

Leakage current at OFF time

100µA or less

Max. voltage down at ON time

1.5V or less

External power

 

Voltage

21.6 to 26.4VDC

supply

 

Current

240mA or less

(For internal circuit)

 

Response time

OFFON

1ms or less

ONOFF

1ms or less 2

 

Surge absorber

 

 

Zener diode

Operating indicator

 

 

LED display

1: 8 points / common (C16T/C16P,E16T/E16P), 16 points / common (C32T/C32P, T32CP, E32T/E32P)

2: 50µs or less at Y0, Y1 only

18

07/2007

 

Image 18
Contents FP0 Series FConP0trol FPWIN- SupPro er Compact PLC From I/O 10-points…Compact size Easy expansion You Save This Much Space…up to 128 I/Os NetworkingFP0 CPU Units Rich Line-Up of Both Single and Combined UnitsRelay output type Input only type Transistor output type FP0 Expansion UnitsChoose the Number of I/O Points to Suit the Applica tion OptionFP0 Impressive Capabilities High Specifica tions for Both Speed and CapacityFP0 Func tions FP0 Communication Serial Int erf aces and Modem Compa tibleMaintenance saving Simple installationEasier Maint enance Than Ever Be fore For Cost Eff ec tive Control of Distribut ed Field Device FP0-DPS specificationsFP0 Profibus DP Slave or Remote I/O Unit ModeDirect connection for reduced wiring Connects Directly to the S-LINK for Reduced WiringFeatures FP0 S-LINK UnitNe tworking Units FP0-IOL Link Unit SpecificationsFP0 MEWNET-F Unit FP0-IOLAnalogue Signal Processing FP0 Analogue UnitsGeneral specifications Analogue input specificationAnalogue output specification Specification Enable High Precision Tempera ture Control a t Low CostFP0-TC4 and FP0-TC8 specifications FP0 Thermocouple Input Expansion UnitsFP0-RTD specifications FP0 RTD Input Expansion UnitAbout the application areas FP0 specifications FP0 SeriesSpecifica tion Tables Input specifications Output specificationsInterfaces Control Fpwin Pro Most important highlights at a glanceFree demonstration CD FP Web-Server HighlightsFP Data Analyzer Control CommX, PCWAY, OPC ServerControl CommX Control FP OPC serverFP0 Control and Expansion Units Produc ts and Order NumbersAnalogue units Temperature control unitsFP0 Analogue and Networking Units Networking unitsAccessories OptionsAdditional parts Control Fpwin Pro Programming software and cablesCurrent consumption list Control Fpwin GRPower Supplies Performance specificationsStandards FP0 Product Overview Order NumbersProduct Name Part Number Global Network