Thermo Products Models from 8 kW to 24 kW : 240 Volts ( single phase ) Adjusting the Mixing Valve

Page 12

4.6 ADJUSTING THE MIXING VALVE

A thermostatically controlled mixing valve works automatically thanks to the thermostatic element controlling the mix of very hot and cold water as required to provide safe domestic hot water under variable conditions.

To adjust the mixing valve setting, carefully open a hot water tap. Protect yourself against the possibility of scalding. Measure the hot water temperature and adjust it with the mixing valve, following the manufacturer’s instructions. Lock the adjusting valve in place at the proper setting.

A higher boiler water temperature setting is now possible thanks to this moderating effect. The boiler water in the COMBOMAXMC tank acts as a buffer and increases the boiler efficiency as well as the amount of domestic hot water produced.

To increase the ad hoc or general hot water production capacity, first adjust the domestic hot water priority aquastat setting (e.g., from 140°F to 180°F), then the mixing valve setting (e.g., from 90°F to 120°F).

Some sanitary uses may require different setting ranges or dedicated piping.

COMBOMAXMC Electric boiler Set-up, use and care guide (revised January 2006), Page 12.

Image 12
Contents Combomax Technical specifications Boiler specifications 240 Vac single phaseBoiler and connection dimensions Domestic hot water production capacity in US gallonsDIMENSION/ Dimensional Local Installation Regulations ChecklistIntroduction Corrosive AtmosphereInstallation Flow-check valve Pressure relief valveOperating pressure control expansion tank Makeup valveConnecting the domestic hot water piping Domestic HOT Water CircuitExpansion tank on the cold water supply line Boiler Wiring Circulator WiringPrioritizing Terminal Post BI-ENERGY Setup Adjusting the Aquastats OperationFilling the Tank Filling the Heating CoilStartup Procedure Domestic HOT Water StartupAdjusting the Mixing Valve Maintenance General Safety Precautions Combomax Schéma dinstallation général/ General installation Système primaire/secondaire TH1 TH2 EL1 EL2 TH1 EL1 TH2 EL2 24 Vac Bi-énergie avec Valve 3 Voies/ Dual Energy with 3-way valve Diagramme électrique/ Wiri ng diagram Thermo 2000 inc Panneau de contrôlel Control pannel Combomax TM Limited Warranty