Thermo Products OD6RA072DV5B Reduction of Clearances with Specified Forms of Protection

Page 12

Fig. 6: Suggested method to accommodate vent connector passage through a wall composed of a combustible material.

Fig. 7: Alternate constructions that allow reduced clearances to combustible materials.

REDUCTION OF CLEARANCES WITH SPECIFIED FORMS OF PROTECTION:

Type of protection applied to and covering all surfaces of combustible material within the distance specified as the required clearance with no protection unless otherwise noted, all dimensions in inches, refer to Fig. 7.

Required clearance with no protection from the appliance or

18 inches

9 inches

6 inches

Sides &

Sides &

Sides &

chimney connector is:

 

 

Above Rear

Above Rear

Rear

a.

3-1/2" thick masonry wall without ventilation air space….

--

12

--

6

--

5

b. 1/2" insulation board over 1" glass fiber or mineral wool batts…

12

9

6

5

4

3

c. 0.024(24 gauge) sheet metal over 1" glass fiber or mineral

 

 

 

 

 

 

wool batts reinforced with wire on rear face with ventilated air

 

 

 

 

 

 

space…

9

6

5

3

3

3

d.

3- 1/2" thick masonry wall with ventilation air space..

--

6

--

6

--

6

e.

0.024 (24 gauge) sheet metal with ventilated air space.

9

6

5

3

3

2

f. 1/2" thick insulation board with ventilation air space..

9

6

5

3

3

3

g. 0.024 ( 24 gauge) sheet metal with ventilated air space over

 

 

 

 

 

 

0.024 (24 gauge) sheet metal with ventilated air space….

9

6

5

3

3

3

h. 1" glass fiber or mineral wool batts sandwiched between two

 

 

 

 

 

 

sheets 0.024 (24 gauge) sheet metal with ventilated air space

9

6

5

3

3

3

A.Equal the required clearance with no protection.

B.Equals the reduced clearance permitted in accordance with the preceding clearance chart.

C.The protection applied to the construction that covers the combustible material should extend far enough in each direction to make C equal to A.

9

Image 12
Contents OD6FA072D48B OD6RA072D48B OD6FX072DV5R OD6FA072DV5B OD6RA072DV5B OD6RX072DV5ROD6FA072D48R OD6RA072D48R OD6FA072DV5R OD6RA075DV5RContents = Highboy D = Downflow = Front = RearSafety Section Page Codes and Clearances Combustible materialNon-combustible material II. General Instructions Read Before Start of Installation Counterflow OD6F*072D Horizontal OD6R*072DChimney Proper Chimney SizePrevention of Chimney Condensing Proper Vent Connector PIPE/CHIMNEY Connection Proper Chimney HeightTight CLEAN-OUT Doors and Connections Tight JointsNo Interconnected Chimney Flues Flue Pipe CLEARANCES, Sizing and TypeReduction of Clearances with Specified Forms of Protection Venting Rotation of Front Flue Elbow 15’ application MAXDraft Regulators Duct WORK/AIR ConditioningAirflow Requirements and Sizing of Duct Work Page Page Examples Air Filters Maximum Filter Type Air Velocity Model Number Ft/minOD6 Burner Installation This retainer when installing burnerLimit Position and Location Page Page Burner Specifications and Applications Burner insertion illustration Top viewRiello 2-stage burner specifications and applications Beckett RielloMounting the 2-STAGE Riello Burner BTU/HR Heating CapacityOIL Tank and Piping OIL Filter Electrical WiriingElectronic Air Cleaner EAC and Humidifier Installation Thermostat Anticipator Setting Fan Control ModulePreferred method of adjustment Heat Anticipator Adjustment ScaleBlower Motor Speed Selection Heating Speed Set-ups Single Stage CFMHeating Speed Set-ups 2 Stage LOW Capacity High CapacityCooling blower motor speed chart Cooling Speed Set-upsHeating speed by input Terminal Definitions & Field Wiring Blower Controller Information for PSC MotorInputs OutputsOperating Modes On and OFF Blower Delay Time Switch Settings PSC Trouble Shooting Diagnostic FeaturesStartup Procedures STOP! Read the safety information aboveOperating Instructions Adjustment of Burner Combustion To Turn Off Oil to ApplianceCombustion Head Setting for 2-STAGE Riello Burner Preliminary Adjustment of Burner Air Band and Air ShutterAIR Damper Adjustment Turn to the Right Sign +Turn to the Left Sign 1st Stage Adjustment 2nd Stage AdjustmentAdjustment Of Heat Input Rate Page Checkout Procedure III. Users Information Section Inspection AreasFilter Cleaning and Location Starting the BurnerIV. Installers Instructions to User Dealer Maintenance Safety During Servicing and InspectionGeneral Inspection Heat Exchanger Cleaning Instructions Heat ExchangerHeat Exchanger Clean-Outs Filter maintenance procedure Electrical SystemSUPPLY/RETURN AIR Blower SUPPLY/RETURN AIR FilterFilter replacement Extended Appliance ShutdownOn Shutdown On StartupVI. HOMEOWNER/USER Information and Routine Maintenance Location of oil primary control reset button Beckett Burner Riello BurnerDiagnostics Diagnostic FeaturesNumber of flashes Cad Cell Resistance in ohms Model R7184B CAD Cell Checkout Procedure VIII. Sequence of Operations Flow Chart Page IX. Trouble Shooting Flow Chart Page Page Page Page Customer Appendix a Replacement Parts Page Replacement Parts for OD6R*072D Page Appendix B Wiring Diagrams OD6*A072DV5 ECM Wiring Diagram OD6*X072DV5 ECM 2-Stage Wiring Diagram

OD6FA072D48B, OD6FA072DV5B, OD6RA075DV5R, OD6FA072D48R, OD6RA072D48R specifications

The Thermo Products range, which includes models OD6RA072DV5B, OD6RA072D48R, OD6FA072DV5R, OD6RA072D48B, and OD6RX072DV5R, represents an advanced line of HVAC solutions designed for efficient heating and cooling performance. These models are tailored to meet the rigorous demands of both residential and commercial environments, combining innovative technologies with user-friendly features.

One of the standout features across these models is their enhanced energy efficiency. Utilizing advanced inverter technology, these units adjust their compressor speed to meet the precise heating or cooling demand, significantly reducing energy consumption and operational costs. Their Energy Star certification reflects their ability to perform optimally while minimizing environmental impact.

The OD6RA072DV5B and OD6RA072D48R models are particularly noted for their robust cooling capabilities, powered by cutting-edge refrigerant technology that allows for rapid cooling in even the hottest conditions. This is complemented by a multi-stage filtration system that not only improves air quality but also ensures a consistent airflow rate, reducing strain on the system.

In terms of installation and operation, these models are designed with user convenience in mind. The compact design allows for easy installation in a variety of settings, while the integrated smart controls enable remote monitoring and adjustments via mobile devices. This connectivity enhances user experience, providing real-time feedback on system performance.

The OD6FA072DV5R and OD6RA072D48B models are specifically engineered for superior quiet operation, incorporating sound-dampening technologies that minimize noise levels. This makes them an excellent choice for residential areas or spaces where noise reduction is a priority.

Durability and reliability are central characteristics of these Thermo Products models. Constructed with high-quality materials and protected against environmental factors, they have a longer lifespan compared to traditional HVAC systems. With a robust warranty program, users can have peace of mind knowing they are supported by a reliable product.

Overall, the Thermo Products line offers a competitive range of HVAC solutions. With their impressive efficiency ratings, advanced technologies, and user-centric features, models like the OD6RA072DV5B, OD6RA072D48R, OD6FA072DV5R, OD6RA072D48B, and OD6RX072DV5R stand as a testament to innovation in the heating and cooling industry.