Thermo Products OD6RA072D48R, OD6FA072DV5R, OD6RX072DV5R, OD6RA072DV5B, OD6FX072DV5R, OD6RA072D48B

Page 15

2.To reduce the transmission of vibration and noise to the duct system and to reduce flexure of the duct system due to thermal expansion and contraction, it is recommended that flexible joints be installed at the supply and return duct connections to the unit.

3.The return air duct system must equal the supply air duct system in the flow capacity (CFM) for a given pressure drop. Use a supplier's catalog for proper sizing of outlet and return air registers and grills to ensure that they meet the flow requirements of the run to which they are connected.

4.The duct system shall be sized to provide the maximum air flowrate (CFM) required of the installation. Two common rules for determining minimum airflow in heating and cooling systems follow:

a.For heating, 14 CFM of airflow are required per 1000 BTU/hr of heat output, based on steady state operation and a 50° to 80° temperature rise.

b.For cooling, 400 CFM of airflow are required per ton of air conditioning. (For reference, a ton of A/C = 12,000 BTU/hr removed from the space.)

Refer to Example 1, (page 14) for a sample calculation of how to determine the required minimum air flowrate.

5.Duct sizing is based upon both air velocity and pressure drop considerations. When possible, current practice favors designing ductwork for lower air velocities. (For residences, a maximum air velocity of 800 FPM is suggested.) This results in quieter duct systems, systems which require less fan power (reduced operating costs), and less carefully constructed ductwork (lower initial costs).

However, lower air velocities also result in larger duct sizes than necessary at higher velocities. In some cases, space restrictions may limit the ductwork to smaller than optimal sizes.

6.The following method can be used to size ductwork when air velocities are low to moderate.

a.Using a floor view of the residence, determine, or layout, the locations of the supply registers and the return air grills. (Generally, supply registers should be located close to sources of heat loss, i.e. windows and doors, around the perimeter of the building. Return grills should be located in central positions as far away from the supply registers as practical.)

b.Find a location for the appliance that minimizes the amount of ducting required to connect the appliance to the supply and return air duct systems. Consider issues of access to the oil supply and electrical service, required service and venting clearances, and operating noise when selecting this location.

c.Plan an efficient layout for the ductwork connecting each of the supply air registers in the supply system to the unit. Plan and layout ductwork connecting each of the return air grills in the return system to the unit. Measure or estimate the length of duct between each register and grill.

d.Select values for the airflow through each register and grill.

e.Select values for the pressure drops of both the supply and return air systems. Each branch of the supply (or the return) air system will have this pressure drop. The total pressure drop of the supply and return air systems added together cannot exceed the maximum external static pressure that can be supplied by the appliance blower.

f.Determine the required flowrate for each branch of the supply and return air systems. The total air flowrate, by adding the air flowrate of each branch of the supply system, must equal the minimum required air flowrate (refer to part 3, above). Likewise, the air flowrate of each of the branches of the return air system must sum to the required minimum flowrate.

g.Using the selected air flowrates for each component of the duct system and manufacturer’s literature, or published literature on duct system pressure drops, the pressure drop for each component in the duct system can be estimated.

12

Image 15
Contents OD6FA072DV5R OD6RA075DV5R OD6FA072D48B OD6RA072D48B OD6FX072DV5ROD6FA072DV5B OD6RA072DV5B OD6RX072DV5R OD6FA072D48R OD6RA072D48RContents = Front = Rear = Highboy D = DownflowSafety Section Page Combustible material Codes and ClearancesNon-combustible material Counterflow OD6F*072D Horizontal OD6R*072D II. General Instructions Read Before Start of InstallationChimney Proper Chimney SizePrevention of Chimney Condensing Proper Chimney Height Proper Vent Connector PIPE/CHIMNEY ConnectionFlue Pipe CLEARANCES, Sizing and Type Tight CLEAN-OUT Doors and ConnectionsTight Joints No Interconnected Chimney FluesReduction of Clearances with Specified Forms of Protection 15’ application MAX Venting Rotation of Front Flue ElbowDraft Regulators Duct WORK/AIR ConditioningAirflow Requirements and Sizing of Duct Work Page Page Examples Air Filters Maximum Filter Type Air Velocity Model Number Ft/minOD6 Burner Installation This retainer when installing burnerLimit Position and Location Page Page Burner insertion illustration Top view Burner Specifications and ApplicationsBeckett Riello Riello 2-stage burner specifications and applicationsBTU/HR Heating Capacity Mounting the 2-STAGE Riello BurnerOIL Tank and Piping Electrical Wiriing OIL FilterElectronic Air Cleaner EAC and Humidifier Installation Fan Control Module Thermostat Anticipator SettingHeat Anticipator Adjustment Scale Preferred method of adjustmentBlower Motor Speed Selection CFM Heating Speed Set-ups Single StageLOW Capacity High Capacity Heating Speed Set-ups 2 StageCooling Speed Set-ups Cooling blower motor speed chartHeating speed by input Blower Controller Information for PSC Motor Terminal Definitions & Field WiringOutputs InputsOperating Modes On and OFF Blower Delay Time Switch Settings Diagnostic Features PSC Trouble ShootingStartup Procedures STOP! Read the safety information aboveOperating Instructions To Turn Off Oil to Appliance Adjustment of Burner CombustionPreliminary Adjustment of Burner Air Band and Air Shutter Combustion Head Setting for 2-STAGE Riello BurnerAIR Damper Adjustment Turn to the Right Sign +Turn to the Left Sign 2nd Stage Adjustment 1st Stage AdjustmentAdjustment Of Heat Input Rate Page Checkout Procedure Inspection Areas III. Users Information SectionStarting the Burner Filter Cleaning and LocationIV. Installers Instructions to User Dealer Maintenance Safety During Servicing and InspectionGeneral Inspection Heat Exchanger Heat Exchanger Cleaning InstructionsHeat Exchanger Clean-Outs SUPPLY/RETURN AIR Filter Filter maintenance procedureElectrical System SUPPLY/RETURN AIR BlowerExtended Appliance Shutdown Filter replacementOn Startup On ShutdownVI. HOMEOWNER/USER Information and Routine Maintenance Beckett Burner Riello Burner Location of oil primary control reset buttonDiagnostics Diagnostic FeaturesNumber of flashes Cad Cell Resistance in ohms Model R7184B CAD Cell Checkout Procedure VIII. Sequence of Operations Flow Chart Page IX. Trouble Shooting Flow Chart Page Page Page Page Customer Appendix a Replacement Parts Page Replacement Parts for OD6R*072D Page Appendix B Wiring Diagrams OD6*A072DV5 ECM Wiring Diagram OD6*X072DV5 ECM 2-Stage Wiring Diagram

OD6FA072D48B, OD6FA072DV5B, OD6RA075DV5R, OD6FA072D48R, OD6RA072D48R specifications

The Thermo Products range, which includes models OD6RA072DV5B, OD6RA072D48R, OD6FA072DV5R, OD6RA072D48B, and OD6RX072DV5R, represents an advanced line of HVAC solutions designed for efficient heating and cooling performance. These models are tailored to meet the rigorous demands of both residential and commercial environments, combining innovative technologies with user-friendly features.

One of the standout features across these models is their enhanced energy efficiency. Utilizing advanced inverter technology, these units adjust their compressor speed to meet the precise heating or cooling demand, significantly reducing energy consumption and operational costs. Their Energy Star certification reflects their ability to perform optimally while minimizing environmental impact.

The OD6RA072DV5B and OD6RA072D48R models are particularly noted for their robust cooling capabilities, powered by cutting-edge refrigerant technology that allows for rapid cooling in even the hottest conditions. This is complemented by a multi-stage filtration system that not only improves air quality but also ensures a consistent airflow rate, reducing strain on the system.

In terms of installation and operation, these models are designed with user convenience in mind. The compact design allows for easy installation in a variety of settings, while the integrated smart controls enable remote monitoring and adjustments via mobile devices. This connectivity enhances user experience, providing real-time feedback on system performance.

The OD6FA072DV5R and OD6RA072D48B models are specifically engineered for superior quiet operation, incorporating sound-dampening technologies that minimize noise levels. This makes them an excellent choice for residential areas or spaces where noise reduction is a priority.

Durability and reliability are central characteristics of these Thermo Products models. Constructed with high-quality materials and protected against environmental factors, they have a longer lifespan compared to traditional HVAC systems. With a robust warranty program, users can have peace of mind knowing they are supported by a reliable product.

Overall, the Thermo Products line offers a competitive range of HVAC solutions. With their impressive efficiency ratings, advanced technologies, and user-centric features, models like the OD6RA072DV5B, OD6RA072D48R, OD6FA072DV5R, OD6RA072D48B, and OD6RX072DV5R stand as a testament to innovation in the heating and cooling industry.