Thermo Products OD6RA075DV5R, OD6FA072DV5R Electronic Air Cleaner EAC and Humidifier Installation

Page 27

 

 

 

 

Maximum

 

 

 

 

Oil Burner

Time Delay

Minimum

 

Potential/Frequenc

Supply/Return

Assembly

Type Fuse

Recommende

Model

Air Blower Full

Full Load

or Inverse

d 75 deg. C.

y/No. of Phases

Load Current

Current

Time

Copper

 

(V/Hz/Ph)

(Amps) @ 115

Circuit

 

(Amps) @

Power Wiring

 

 

VAC

115 VAC

Breaker

Size (AWG)

 

 

 

Size

 

 

 

 

 

 

 

 

 

(Amps)

 

OD6**072D48

120/60/1

7.5 PSC

1.7

15

12

OD6**072DV5

10.1 ECM

15

12

 

 

Table 10: Typical Electrical Requirements for Various OD6 Models

Wire size selections in Table 10 are based upon Table 310-16 of the National Electrical Code for three copper conductors, with insulation rated for 75 degrees Celsius, contained in raceway at 30 degrees Celsius. For other wire insulation temperature ratings and ambient conditions, refer to the National Electrical Code for the minimum wire sizing requirements.

NOTICE: Before the unit is started, the installer and/or electrician must check the following items:

1.Check every electrical connection of “push-on” or “screw-on” type terminals to ensure that all wires and wire connectors are firmly secured. A loose terminal can cause poor flow of electrical power to motors. This may result in very high current draws by these components. If great enough, high current draw will cause blown fuses, burned wires and contactor points, and pre- mature motor failure. Each electrical connection has been factory checked, however, connections may loosen, due to vibration, while the appliance is in transit. Please be certain that all electrical connections remain tight.

2.Review wiring diagram for proper routing and connection of all field wiring.

3.All wiring sizes must comply with local codes or the National Electrical Code. To minimize voltage drop to the appliance, the next larger size wire should be used when long wiring runs, in excess of 100 ft., are employed. Refer to the wiring diagrams when wiring or servicing.

In the event a circuit breaker trips or a fuse blows as a result of the operation of this appliance, investigate the appliance electrical system to determine the cause. Correct any electrical faults and abnormal conditions before putting the unit back into operation. Do not put in a larger fuse and do not exceed maximum fuse size listed on the rating label in order to temporarily “fix” the problem. The rating label is located on the inside of the burner compartment cover.

Electronic Air Cleaner (EAC) and Humidifier Installation:

The fan timer on this unit has designated terminals to control the operation of an electronic air cleaner and/or humidifier. These terminals provide line voltage for the control of these accessories, refer to Figure 15 on the next page. Connection between EAC and N6 provides a switched 115 vac to power an electronic fan cleaner. The same switched 115 vac is available between EAC and N7 and may be used in conjunction with a humidistat to control a humidifier. These terminals are energized whenever the blower is active.

24

Image 27
Contents OD6FA072DV5R OD6RA075DV5R OD6FA072D48B OD6RA072D48B OD6FX072DV5ROD6FA072DV5B OD6RA072DV5B OD6RX072DV5R OD6FA072D48R OD6RA072D48RContents = Front = Rear = Highboy D = DownflowSafety Section Page Combustible material Codes and ClearancesNon-combustible material Counterflow OD6F*072D Horizontal OD6R*072D II. General Instructions Read Before Start of InstallationChimney Proper Chimney SizePrevention of Chimney Condensing Proper Chimney Height Proper Vent Connector PIPE/CHIMNEY ConnectionFlue Pipe CLEARANCES, Sizing and Type Tight CLEAN-OUT Doors and ConnectionsTight Joints No Interconnected Chimney FluesReduction of Clearances with Specified Forms of Protection 15’ application MAX Venting Rotation of Front Flue ElbowDraft Regulators Duct WORK/AIR ConditioningAirflow Requirements and Sizing of Duct Work Page Page Examples Air Filters Maximum Filter Type Air Velocity Model Number Ft/minOD6 Burner Installation This retainer when installing burnerLimit Position and Location Page Page Burner insertion illustration Top view Burner Specifications and ApplicationsBeckett Riello Riello 2-stage burner specifications and applicationsBTU/HR Heating Capacity Mounting the 2-STAGE Riello BurnerOIL Tank and Piping Electrical Wiriing OIL FilterElectronic Air Cleaner EAC and Humidifier Installation Fan Control Module Thermostat Anticipator SettingHeat Anticipator Adjustment Scale Preferred method of adjustmentBlower Motor Speed Selection CFM Heating Speed Set-ups Single StageLOW Capacity High Capacity Heating Speed Set-ups 2 StageCooling Speed Set-ups Cooling blower motor speed chartHeating speed by input Blower Controller Information for PSC Motor Terminal Definitions & Field WiringOutputs InputsOperating Modes On and OFF Blower Delay Time Switch Settings Diagnostic Features PSC Trouble ShootingStartup Procedures STOP! Read the safety information aboveOperating Instructions To Turn Off Oil to Appliance Adjustment of Burner CombustionPreliminary Adjustment of Burner Air Band and Air Shutter Combustion Head Setting for 2-STAGE Riello BurnerAIR Damper Adjustment Turn to the Right Sign +Turn to the Left Sign 2nd Stage Adjustment 1st Stage AdjustmentAdjustment Of Heat Input Rate Page Checkout Procedure Inspection Areas III. Users Information SectionStarting the Burner Filter Cleaning and LocationIV. Installers Instructions to User Dealer Maintenance Safety During Servicing and InspectionGeneral Inspection Heat Exchanger Heat Exchanger Cleaning InstructionsHeat Exchanger Clean-Outs SUPPLY/RETURN AIR Filter Filter maintenance procedureElectrical System SUPPLY/RETURN AIR BlowerExtended Appliance Shutdown Filter replacementOn Startup On ShutdownVI. HOMEOWNER/USER Information and Routine Maintenance Beckett Burner Riello Burner Location of oil primary control reset buttonDiagnostics Diagnostic FeaturesNumber of flashes Cad Cell Resistance in ohms Model R7184B CAD Cell Checkout Procedure VIII. Sequence of Operations Flow Chart Page IX. Trouble Shooting Flow Chart Page Page Page Page Customer Appendix a Replacement Parts Page Replacement Parts for OD6R*072D Page Appendix B Wiring Diagrams OD6*A072DV5 ECM Wiring Diagram OD6*X072DV5 ECM 2-Stage Wiring Diagram

OD6FA072D48B, OD6FA072DV5B, OD6RA075DV5R, OD6FA072D48R, OD6RA072D48R specifications

The Thermo Products range, which includes models OD6RA072DV5B, OD6RA072D48R, OD6FA072DV5R, OD6RA072D48B, and OD6RX072DV5R, represents an advanced line of HVAC solutions designed for efficient heating and cooling performance. These models are tailored to meet the rigorous demands of both residential and commercial environments, combining innovative technologies with user-friendly features.

One of the standout features across these models is their enhanced energy efficiency. Utilizing advanced inverter technology, these units adjust their compressor speed to meet the precise heating or cooling demand, significantly reducing energy consumption and operational costs. Their Energy Star certification reflects their ability to perform optimally while minimizing environmental impact.

The OD6RA072DV5B and OD6RA072D48R models are particularly noted for their robust cooling capabilities, powered by cutting-edge refrigerant technology that allows for rapid cooling in even the hottest conditions. This is complemented by a multi-stage filtration system that not only improves air quality but also ensures a consistent airflow rate, reducing strain on the system.

In terms of installation and operation, these models are designed with user convenience in mind. The compact design allows for easy installation in a variety of settings, while the integrated smart controls enable remote monitoring and adjustments via mobile devices. This connectivity enhances user experience, providing real-time feedback on system performance.

The OD6FA072DV5R and OD6RA072D48B models are specifically engineered for superior quiet operation, incorporating sound-dampening technologies that minimize noise levels. This makes them an excellent choice for residential areas or spaces where noise reduction is a priority.

Durability and reliability are central characteristics of these Thermo Products models. Constructed with high-quality materials and protected against environmental factors, they have a longer lifespan compared to traditional HVAC systems. With a robust warranty program, users can have peace of mind knowing they are supported by a reliable product.

Overall, the Thermo Products line offers a competitive range of HVAC solutions. With their impressive efficiency ratings, advanced technologies, and user-centric features, models like the OD6RA072DV5B, OD6RA072D48R, OD6FA072DV5R, OD6RA072D48B, and OD6RX072DV5R stand as a testament to innovation in the heating and cooling industry.