Thermo Products OD6RA072D48B, OD6FA072DV5R 1st Stage Adjustment, 2nd Stage Adjustment

Page 44

Figure 22

1st STAGE ADJUSTMENT:

Adjustment of air shutter: place the small plug (9) of the economizer (10) into the position I (Item A). In this way the burner will remain permanently in the 1st stage.

Loosen the nut (2), turn the screw (3) until the air shutter (1) reaches the position desired. Then lock the nut (2).

Pressure regulation: this is set at 130 psi at the factory. Should such pressure be reset or changed, just turn the screw (4). The pressure gauge must be mounted in place of cap (5).

2nd STAGE ADJUSTMENT:

Adjustment of air shutter: place the small plug (9) of the economizer (10) into the position II (Item B). In this way the burner remains permanently in the 2nd stage. Loosen the nut (6), turn the screw (7) until the air shutter (1) reaches the position desired. Then lock the nut (6).

Pressure regulation: this is set at 170 psi at the factory. Should such pressure be reset or changed, just turn the screw (8). The pressure gauge must be mounted in place of cap (5).

i.SMOKE: A smoke sample should be drawn from the heat exchanger flue passageway, which is covered by the vent terminal. (Remove a large machine screw from the front face of the vent terminal for direct access to the flue through the opening.) If the first smoke reading is zero (0), close the air band, or shutter, on the burner until a trace smoke reading is measured.

NOTICE: To achieve proper combustion and the efficiencies listed in sales brochures, instruments must be used to secure CO2 or O2 readings.

41

Image 44
Contents OD6FA072D48B OD6RA072D48B OD6FX072DV5R OD6FA072DV5B OD6RA072DV5B OD6RX072DV5ROD6FA072D48R OD6RA072D48R OD6FA072DV5R OD6RA075DV5RContents = Highboy D = Downflow = Front = RearSafety Section Page Codes and Clearances Combustible materialNon-combustible material II. General Instructions Read Before Start of Installation Counterflow OD6F*072D Horizontal OD6R*072DPrevention of Chimney Condensing ChimneyProper Chimney Size Proper Vent Connector PIPE/CHIMNEY Connection Proper Chimney HeightTight CLEAN-OUT Doors and Connections Tight JointsNo Interconnected Chimney Flues Flue Pipe CLEARANCES, Sizing and TypeReduction of Clearances with Specified Forms of Protection Venting Rotation of Front Flue Elbow 15’ application MAXAirflow Requirements and Sizing of Duct Work Draft RegulatorsDuct WORK/AIR Conditioning Page Page Examples OD6 Air FiltersMaximum Filter Type Air Velocity Model Number Ft/min Limit Position and Location Burner InstallationThis retainer when installing burner Page Page Burner Specifications and Applications Burner insertion illustration Top viewRiello 2-stage burner specifications and applications Beckett RielloMounting the 2-STAGE Riello Burner BTU/HR Heating CapacityOIL Tank and Piping OIL Filter Electrical WiriingElectronic Air Cleaner EAC and Humidifier Installation Thermostat Anticipator Setting Fan Control ModulePreferred method of adjustment Heat Anticipator Adjustment ScaleBlower Motor Speed Selection Heating Speed Set-ups Single Stage CFMHeating Speed Set-ups 2 Stage LOW Capacity High CapacityCooling blower motor speed chart Cooling Speed Set-upsHeating speed by input Terminal Definitions & Field Wiring Blower Controller Information for PSC MotorInputs OutputsOperating Modes On and OFF Blower Delay Time Switch Settings PSC Trouble Shooting Diagnostic FeaturesOperating Instructions Startup ProceduresSTOP! Read the safety information above Adjustment of Burner Combustion To Turn Off Oil to ApplianceCombustion Head Setting for 2-STAGE Riello Burner Preliminary Adjustment of Burner Air Band and Air ShutterTurn to the Left Sign AIR Damper AdjustmentTurn to the Right Sign + 1st Stage Adjustment 2nd Stage AdjustmentAdjustment Of Heat Input Rate Page Checkout Procedure III. Users Information Section Inspection AreasFilter Cleaning and Location Starting the BurnerIV. Installers Instructions to User General Inspection Dealer MaintenanceSafety During Servicing and Inspection Heat Exchanger Cleaning Instructions Heat ExchangerHeat Exchanger Clean-Outs Filter maintenance procedure Electrical SystemSUPPLY/RETURN AIR Blower SUPPLY/RETURN AIR FilterFilter replacement Extended Appliance ShutdownOn Shutdown On StartupVI. HOMEOWNER/USER Information and Routine Maintenance Location of oil primary control reset button Beckett Burner Riello BurnerNumber of flashes Cad Cell Resistance in ohms Model R7184B DiagnosticsDiagnostic Features CAD Cell Checkout Procedure VIII. Sequence of Operations Flow Chart Page IX. Trouble Shooting Flow Chart Page Page Page Page Customer Appendix a Replacement Parts Page Replacement Parts for OD6R*072D Page Appendix B Wiring Diagrams OD6*A072DV5 ECM Wiring Diagram OD6*X072DV5 ECM 2-Stage Wiring Diagram

OD6FA072D48B, OD6FA072DV5B, OD6RA075DV5R, OD6FA072D48R, OD6RA072D48R specifications

The Thermo Products range, which includes models OD6RA072DV5B, OD6RA072D48R, OD6FA072DV5R, OD6RA072D48B, and OD6RX072DV5R, represents an advanced line of HVAC solutions designed for efficient heating and cooling performance. These models are tailored to meet the rigorous demands of both residential and commercial environments, combining innovative technologies with user-friendly features.

One of the standout features across these models is their enhanced energy efficiency. Utilizing advanced inverter technology, these units adjust their compressor speed to meet the precise heating or cooling demand, significantly reducing energy consumption and operational costs. Their Energy Star certification reflects their ability to perform optimally while minimizing environmental impact.

The OD6RA072DV5B and OD6RA072D48R models are particularly noted for their robust cooling capabilities, powered by cutting-edge refrigerant technology that allows for rapid cooling in even the hottest conditions. This is complemented by a multi-stage filtration system that not only improves air quality but also ensures a consistent airflow rate, reducing strain on the system.

In terms of installation and operation, these models are designed with user convenience in mind. The compact design allows for easy installation in a variety of settings, while the integrated smart controls enable remote monitoring and adjustments via mobile devices. This connectivity enhances user experience, providing real-time feedback on system performance.

The OD6FA072DV5R and OD6RA072D48B models are specifically engineered for superior quiet operation, incorporating sound-dampening technologies that minimize noise levels. This makes them an excellent choice for residential areas or spaces where noise reduction is a priority.

Durability and reliability are central characteristics of these Thermo Products models. Constructed with high-quality materials and protected against environmental factors, they have a longer lifespan compared to traditional HVAC systems. With a robust warranty program, users can have peace of mind knowing they are supported by a reliable product.

Overall, the Thermo Products line offers a competitive range of HVAC solutions. With their impressive efficiency ratings, advanced technologies, and user-centric features, models like the OD6RA072DV5B, OD6RA072D48R, OD6FA072DV5R, OD6RA072D48B, and OD6RX072DV5R stand as a testament to innovation in the heating and cooling industry.