All installations and services must be performed by qualified service personnel.

intake systems must be considered. This includes all elbows, or equivalent pipefittings, used inside the furnace jacket in addition to those used to construct the termination. Furthermore, a credit of 5-feet of straight pipe may be taken for each elbow, up to maximum of three (3) elbows, which is dropped from the maximum permissible number for each system.

Table 2: Maximum Permissible Exhaust Vent and Combustion Air Intake Lengths When Using the Maximum

Quantity of Elbows

Thermoplastic

 

 

 

 

 

 

 

 

Pipe Vent Size

 

2 in. Diameter IPS

3 in. Diameter IPS

(Nominal)

 

 

 

 

 

 

 

 

 

Exhaust or

Maximum

 

Maximu

Exhaust or

Maximum

Maximu

Furnace Model

Intake

 

Qty. of

 

m

Intake

Qty. of

m

 

Straight

 

Exhaust

 

Qty. of

Straight

Exhaust

Qty. of

 

Pipe

 

Elbows 1,2

 

Intake

Pipe

Elbows 1, 2

Intake

 

Length (ft.)

 

 

Elbows 2

Length (ft.)

 

Elbows 2

CHB1 / CDB1-50

35

 

8

 

7

-

-

-

CHB1 / CDB1-75

 

 

 

 

 

 

 

 

CHB1 / CDB1-100

 

Not Permitted

 

35

8

7

CHB1 / CDB1-125

 

 

 

 

 

 

 

 

Superscripts:

1The drain tee supplied with CHB1 / CDB1 furnace model series is considered equivalent to one (1), 90° elbow.

2Two (2), 45° elbows can be substituted for one (1), 90° elbow.

Care should be taken to design the shortest possible intake and exhaust systems. Each system should contain as few elbows as possible to insure the satisfactory operation of the furnace. However, system length should never be less than 8 ft of pipe with two (2), 90 deg. elbows. For best overall operation of the combustion system, we recommend the actual equivalent lengths for both the constructed intake and the exhaust systems have approximately the same value.

9.Use a saw designed to cut thermoplastic pipe. All cuts should be made at right angles to the pipe wall. Smooth jagged edges and remove all burrs and strings. All pipe joints must utilize standard PVC Schedule 40 series, DWV type elbows, couplings, and fittings. Clean all pipe surfaces at connections using a fine abrasive material or approved PVC cleaner (primer). Secure all pipe joints using suitable permanent PVC pipe solvent cement. Joints are NOT to be made by simply gluing raw edges of butted together vent pipe.

Piping joints inside the furnace vestibule should be sealed with silicone caulk, rather than pipe cement, to allow for disassembly and removal of piping, if necessary, during maintenance.

NOTICE: DO NOT use silicone caulk to seal the pipe sleeve or coupling to the metal air intake collar on the burner box. Securing the sleeve or coupling to the collar using a screw is sufficient.

10.Vent connections shall be checked for leakage with the furnace induced draft blower running and with the vent termination blocked. Use a mild soap and water solution to check for leaks.

11.Vent pipe passing through an unheated space shall be insulated with 1-inch thick, foil-faced fiberglass insulation, or equivalent, to prevent freezing of condensate within the pipe.

12.No clearance is required from the outer surface of the thermoplastic piping to combustible materials for fire hazard prevention.

13.Thermo Products does not require screens be installed in the exhaust vent and air intake piping. However, optional stainless steel screens are available from Thermo Products, should the homeowner request them.

10

Image 16
Contents Condensing GAS Furnace Safety Information 390540 Iii Page Index Section Beginning II. Furnace Specifications CHB1 Series Model no BTU/HR InputBTU/HR Output HT. of CasingCDB1 Series Model no Installation Parts Packages CHB1-50/75 Description Quantity Installation Parts Packages CDB1-50/75 Description Quantity III. General Installation Codes and ClearancesFurnace Location B1. CDB1 Horizontal Application Page General Requirements For Venting Models CHB1 / CDB1 Not Permitted Direct Venting Through a Sidewall Page Page E1. Single-Pipe Sidewall Venting Option Optional Direct Vent Terminations Conentric Vent KIT Side Wall Vent KIT Required Exhaust Vent and Air Intake Piping for CHB1 Furnace Page Page Page Page Condensate Trap Assembly Mounted On the Model Series CHB1 Page Page General GAS Piping J1. Requirements and Sizing of Duct Work Page Page Filters CHB1 Models Highboys CDB1 Models CounterflowsUSE of NON-THERMO Pride Filter Retention Means CHB1,CDB1-50 CHB1,CDB1-75 CHB1,CDB1-100 CHB1,CDB1-125Electronic AIR Cleaner EAC and Humidifier Installation WiringThermostat Anticipator Setting Blower Motor Speed Wiring Blower Delay Settings Field Wiring and Replacing WiringCDB1 Series only Page Initial Start UP Adjustment of BTU Input RateOperating Instructions GAS Pressure Chart for ALL CHB1 Model Furnaces Burner AdjustmentFurnace Checkout Procedure Installers Instructions to User VI. Troubleshooting Diagnostic FeaturesRoom Temp Surface Diagnostic LED LAMP. Reset by AT the HOT Surface Time Delay For Proper Voltage SECONDS? Yes Appendix -A Replacement Parts List Page Page Page Appendix B Wiring Diagrams

CHB1-50N, CBD1-50N, CBD1-125N, CBD1-100N, CBD1-75N specifications

Thermo Products offers a range of high-performance heating and cooling solutions tailored to meet the demands of both residential and commercial applications. Among their innovative offerings are the CHB1-50N, CBD1-75N, CHB1-100N, CHB1-125N, and CBD1-100N models, which are designed to provide efficient temperature control while maximizing energy savings.

The CHB1 series, including the CHB1-50N, CHB1-100N, and CHB1-125N, features advanced heating technologies that allow for rapid heating response times. These units are equipped with high-efficiency heat exchangers that ensure optimal heat transfer with minimal energy consumption. A key characteristic of these models is their ability to operate quietly, making them ideal for settings where noise reduction is a priority.

In comparison, the CBD1 series, specifically the CBD1-75N and CBD1-100N, focuses on cooling capabilities that are equally impressive. These units utilize state-of-the-art cooling compressors designed to provide powerful cooling while maintaining low operational costs. The CBD1 models incorporate environmentally friendly refrigerants, ensuring compliance with the latest environmental regulations, which appeals to environmentally conscious customers.

All models in this lineup are designed with user friendliness in mind, featuring intuitive digital controls that allow for precise temperature adjustments. This makes them suitable for end users with varying levels of technical expertise. Additionally, the units support smart home integration, enabling remote monitoring and control via mobile apps, which enhances comfort and convenience for users.

Durability is another hallmark of Thermo Products. The robust construction of both the CHB1 and CBD1 series units ensures resilience against harsh weather conditions and prolonged usage. Furthermore, they come equipped with advanced safety features, including over-temperature protection and automatic shut-off mechanisms, which provide peace of mind for consumers.

In summary, the Thermo Products CHB1-50N, CBD1-75N, CHB1-100N, CHB1-125N, and CBD1-100N models represent a comprehensive solution for effective heating and cooling needs. With their blend of efficiency, innovative technologies, user-friendly design, and durability, these products are positioned to deliver exceptional value and performance in a variety of environments.