Thermo Products CBD1-100N, CHB1-125N, CHB1-75N, CHB1-100N, CBD1-75N Furnace Checkout Procedure

Page 44

All installations and services must be performed by qualified service personnel.

Figure 22

: The CHB1/CDB1 furnace models are an in-shot burner design, which does not require an air shutter adjustment (air shutters are not used) for proper flame characteristics. Burner box access cover must always be secured with all screws in place and tightened before operating furnace.

E. FURNACE CHECKOUT PROCEDURE

Before any system of gas piping is finally put into service, it shall be carefully tested to assure that it is gas tight as indicated in the manual.

NOTICE: All controls on the unit should be checked for proper functioning prior to the qualified service personnel leaving the job site. Specifically the following should be checked:

With furnace in normal heating operation, check to make certain blower will start and stop automatically under control of integrated fan control.

1.Check safety limit control as follows:

a.Shut off incoming power.

b.Block return air opening or disconnect blower motor leads.

c.Restore power to furnace.

d.Set thermostat above room temperature calling for heat.

e.When temperatures are reached in furnace at limit control setting with blower out of operation, burner should shut off.

f.Shut off electrical power.

IMPORTANT: Remove blockage or reconnect blower motor and restore power.

2.Make certain thermostat will automatically start and stop furnace.

3.Block the flue pipe outlet gradually with a flat piece of metal, until the pressure switch functions shutting off the main burners.

4.Block the PVC pipe inlet gradually with a flat piece of metal until pressure switch functions shutting off the main burners.

IMPORTANT: Remove flue air inlet blockage when done.

5.Remove the blower compartment access door with the furnace operating. The door interrupt switch is in the 120 volt circuit and will shut down the entire system. Replace the blower door and the furnace start-up cycle will begin.

38

Image 44
Contents Condensing GAS Furnace Safety Information 390540 Iii Page Index Section Beginning II. Furnace Specifications CHB1 Series Model no BTU/HR InputBTU/HR Output HT. of CasingCDB1 Series Model no Installation Parts Packages CHB1-50/75 Description Quantity Installation Parts Packages CDB1-50/75 Description Quantity III. General Installation Codes and ClearancesFurnace Location B1. CDB1 Horizontal Application Page General Requirements For Venting Models CHB1 / CDB1 Not Permitted Direct Venting Through a Sidewall Page Page E1. Single-Pipe Sidewall Venting Option Optional Direct Vent Terminations Conentric Vent KIT Side Wall Vent KIT Required Exhaust Vent and Air Intake Piping for CHB1 Furnace Page Page Page Page Condensate Trap Assembly Mounted On the Model Series CHB1 Page Page General GAS Piping J1. Requirements and Sizing of Duct Work Page Page Filters CHB1 Models Highboys CDB1 Models CounterflowsUSE of NON-THERMO Pride Filter Retention Means CHB1,CDB1-50 CHB1,CDB1-75 CHB1,CDB1-100 CHB1,CDB1-125Thermostat Anticipator Setting WiringElectronic AIR Cleaner EAC and Humidifier Installation Blower Motor Speed Wiring Blower Delay Settings Field Wiring and Replacing WiringCDB1 Series only Page Operating Instructions Adjustment of BTU Input RateInitial Start UP GAS Pressure Chart for ALL CHB1 Model Furnaces Burner AdjustmentFurnace Checkout Procedure Installers Instructions to User VI. Troubleshooting Diagnostic FeaturesRoom Temp Surface Diagnostic LED LAMP. Reset by AT the HOT Surface Time Delay For Proper Voltage SECONDS? Yes Appendix -A Replacement Parts List Page Page Page Appendix B Wiring Diagrams

CHB1-50N, CBD1-50N, CBD1-125N, CBD1-100N, CBD1-75N specifications

Thermo Products offers a range of high-performance heating and cooling solutions tailored to meet the demands of both residential and commercial applications. Among their innovative offerings are the CHB1-50N, CBD1-75N, CHB1-100N, CHB1-125N, and CBD1-100N models, which are designed to provide efficient temperature control while maximizing energy savings.

The CHB1 series, including the CHB1-50N, CHB1-100N, and CHB1-125N, features advanced heating technologies that allow for rapid heating response times. These units are equipped with high-efficiency heat exchangers that ensure optimal heat transfer with minimal energy consumption. A key characteristic of these models is their ability to operate quietly, making them ideal for settings where noise reduction is a priority.

In comparison, the CBD1 series, specifically the CBD1-75N and CBD1-100N, focuses on cooling capabilities that are equally impressive. These units utilize state-of-the-art cooling compressors designed to provide powerful cooling while maintaining low operational costs. The CBD1 models incorporate environmentally friendly refrigerants, ensuring compliance with the latest environmental regulations, which appeals to environmentally conscious customers.

All models in this lineup are designed with user friendliness in mind, featuring intuitive digital controls that allow for precise temperature adjustments. This makes them suitable for end users with varying levels of technical expertise. Additionally, the units support smart home integration, enabling remote monitoring and control via mobile apps, which enhances comfort and convenience for users.

Durability is another hallmark of Thermo Products. The robust construction of both the CHB1 and CBD1 series units ensures resilience against harsh weather conditions and prolonged usage. Furthermore, they come equipped with advanced safety features, including over-temperature protection and automatic shut-off mechanisms, which provide peace of mind for consumers.

In summary, the Thermo Products CHB1-50N, CBD1-75N, CHB1-100N, CHB1-125N, and CBD1-100N models represent a comprehensive solution for effective heating and cooling needs. With their blend of efficiency, innovative technologies, user-friendly design, and durability, these products are positioned to deliver exceptional value and performance in a variety of environments.