SPX Cooling Technologies Marley MD specifications Specifications

Page 37

Marley / MD CoolingTower / Specifications: Options

Specifications

Specification Value

of utility voltage to the motor. Automatic bypass with an earth ground condition is not allowed. The bypass contactor shall be cycled on and off while operating in bypass, to maintain the set-point temperature of the cold water. The drive design shall be oper- ated as a stand- alone system without the need for a BMS system. Operator controls shall be mounted on the front of the enclo- sure and shall consist of start and stop control, bypass/VFD selector switch, Auto/ Manual selector switch, manual speed con- trol, and solid-state temperature controller. An emergency bypass selector switch inter- nal to the panel allowing the cooling tower fan motor to be run at full speed shall be furnished. To prevent heating problems in the cooling tower fan motor and to assure proper gear box lubrication the VFD system shall de energize the motor once 25% motor speed is reached and cooling is no longer required. The VFD shall include de- icing logic with auto canceling and adjust- able time. Speed in De-Ice mode shall not exceed 50 % motor speed. The cooling tower manufacturer shall supply VFD start- up assistance. Tower vibration testing throughout the speed range is required to identify and lockout any natural frequency vibration levels which may exceed CTI guidelines.

6.4Add the following paragraph in the Mechanical Equipment section when VFD is used with customers Building Management System: A complete UL listed Variable Speed Drive system in a

IP10 indoor, IP52 indoor or IP14 outdoor enclosure shall be provided. The VFD shall use PWM technology with IGBT switching and integrated bypass design. VFD out put switching shall not cause mechanical issues with gearbox teeth or drive shafts. The VFD shall catch a fan spinning in the reverse direction without tripping. The panel shall include a main disconnect with short circuit protection and external operating handle, lockable in the off position for safety. The

VFD system shall receive a speed refer- ence signal from the Building Management System monitoring the tower cold-water temperature. The bypass shall include a complete magnetic bypass circuit and with capability to isolate the VFD when in the bypass mode. Transfer to the bypass mode shall be manual in the event of VFD failure.

Operator controls shall be mounted on the front of the enclosure and shall consist of

37

Image 37
Contents Marley MD Cooling Tower Page Marley / MD CoolingTower / Table of Contents Marley / MD CoolingTower Marley / MD CoolingTower Plan Marley / MD CoolingTower / Engineering Data SchematicSide Elevation MD5008 Single Cell END ElevationDBA Dimensions Side Elevation MD5008 Multicell2371 MD5008MAC2L 3651 MD5010 Single Cell569 140 MD5010PAC1L 3651 3715 MD5010 MulticellMD5010PAC2L 3607 Side Elevation MD5016 Single Cell153 Model Nominal Tons Motor Operating MD5016 TWO or Three Cell MD5016PAC2L MD5016 Four or More Cells DBA Dimensions Design Shipping Weight Model MD5016 Four Cell Quad MD5016PAC4B Supporting Steel Single Cell Marley / MD CoolingTower / Engineering Data SupportView a Supporting Steel Multicell CL Anchor BoltEND-OUTLET Suction Connection SIDE-OUTLET Suction ConnectionSump Section 70 MAX Marley / MD CoolingTower / Engineering Data HoistingIndoor Storage Tank Electric Basin HeatersBlowdown Marley / MD CoolingTower / Engineering Data Water QualityWater Treatment Performance Warranty Marley / MD CoolingTower / Specifications BaseBase Thermal PerformanceConstruction Design LoadingMechanical Equipment Marley / MD CoolingTower / Specifications Base Hot Water Distribution System Fill, Louvers and Drift EliminatorsCasing and Fan Guard Warranty AccessCold Water Collection Basin Specifications Specification Value Marley / MD CoolingTower / Specifications OptionsConvenience and Safety Options Mechanical Access Platform Mechanical Equipment sec Control OptionsVibration Limit Switch Specifications Premium Efficiency Motor Miscellaneous Options Equalizer Flume Weir GatesSound Control Gregorys Bank Worcester WR3 8AB United Kingdom

Marley MD specifications

SPX Cooling Technologies has long been recognized as a leader in the cooling systems industry, and the Marley MD series exemplifies this commitment to innovation and efficiency. The Marley MD line is engineered for performance and versatility, ideal for a wide range of industrial and commercial cooling applications.

One of the defining features of the Marley MD is its advanced, modular design. This modular approach allows for easy scalability, enabling users to customize their cooling solution based on specific operational needs. Each unit can be configured to meet varying cooling loads, making the Marley MD suitable for both small and large facilities.

The Marley MD utilizes state-of-the-art materials, promoting durability and longevity. Constructed with corrosion-resistant components, these units are designed to withstand harsh environmental conditions, ensuring reliable operation over extended periods. The casing often features a combination of high-quality steel and advanced coatings that provide protection against the elements, which is especially important for outdoor installation.

Additionally, the Marley MD incorporates innovative technologies such as drift eliminators and splash bars, which significantly enhance water efficiency. These features minimize water loss and reduce the risk of contaminants entering the cooling system, leading to better overall performance. The design is also optimized for low sound levels, making these systems suitable for use in sensitive environments where noise reduction is a priority.

Energy efficiency is a critical characteristic of the Marley MD. It leverages advanced fan technology and airflow management to enhance cooling performance while minimizing energy consumption. By using high-efficiency motors and variable-speed drives, the Marley MD can operate at optimal levels under varying load conditions, resulting in significant energy savings over traditional cooling systems.

Another vital aspect is the ease of maintenance. The Marley MD is designed for straightforward access, allowing for efficient servicing and reducing downtime during maintenance activities. Features like removable panels and accessible components ensure that technicians can perform routine checks and repairs quickly and efficiently.

In conclusion, the Marley MD by SPX Cooling Technologies stands out due to its modular design, durable construction, advanced water management technologies, energy efficiency, and ease of maintenance. These characteristics make it an excellent choice for any facility looking to optimize its cooling operations while ensuring reliable and sustainable performance.